Danfoss Optyma Slim Pack OP-LSQM Serie Instrucciones página 2

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
Instructions
Optyma™ Slim Pack
OP-LSQM / LSHM / MSXM / MSHM /
MSGM / MSYM / MSBM
Name plate
OP-MSXM068MLW05E
A
114X7068
B
C
Application
MBP
D
Refrigerant
(1) R404A R507 R448A/R449A
R407A/R407F/R452A
E
M.W.P. HP
(1) 28 bar
M.W.P. LP
(1) 7 bar
F
Voltage
230 V ~ 1N ~ 50Hz
LRA
60 A
OIL INSIDE
POE 46
G
Serial No.
064119CG1517
xxxxxxxxxxxxxx
EAN No.
Danfoss A/S, 6430 Nordborg, Denmark
Danfoss Ltd., 22Wycombe End, HP9 1NB, GB
Імпортер:ТОВ з іі "Данфосс ТОВ" 04080, Київ 80, п/с 168, Україна
* For exact values please refer name plate in unit
A: Model
B: Code number
C: Application, Protection
D: Refrigerant
E: Housing Service Pressure (Maximum working
pressure)
F: Supply voltage, Locked Rotor Ampere,
Maximum Continuous Current
G: Serial Number and bar code
Designation system for the Optyma™ Slim Pack range
OP - MSXM
034 ML W05 G
1 2 3 4
5
1
Application
M = MBP
L = LBP
2
Package
Condensing unit family: S = Slim Pack
3
Refrigerant
H = R404A/R507 ;
G = R134a, R513A ;
Q = R452A, R404A/R507
X = R404A/R507, R134a, R407A, R407F, R448A, R513A,
R449A,R452A ;
Y = R404A/R507, R448A, R449A;
B = R404A/R507, R449A, R452A;
P = R448A/R449A, R407A/F, R404A/R507,
O = R452A, R404A/R507, R448A, R449A
4
Condenser
M = Microchannel heat condenser
5
Swept volume
Displacement in cm
3:
Example 034 = 34 cm
6
Compressor platform
MLZ, LLZ = Scroll Compressor
MTZ & NTZ = Reciprocating Compressor
7
Version
W05/W09: Optyma™ Slim Pack
8
Voltage code
G = 230V/1-phase compressor & 230V/1 phase fan
E = 400V/3-phase compressor & 230V/1-phase fan
2 | AN23308644013405-001501 - 118A0549D
MADE IN INDIA
IP 54
(2) R134a
R513A
N
(2) 23 bar
(2) 5 bar
Max Ref Qty 5.4 kg
MCC 19 A
RLA
8.3 A
PS
28 bar
HP
Picture 1 : Minimum mounting distances
L
[mm]
250
6
7
8
3
L
O
M
M
N
O
[mm]
[mm]
[mm]
650
550
550
Version control
Optyma™ Slim Pack
IP level
Compressor technology
Control box (pre-wired E-panel)
Microchannel condenser
Fan speed controller
Main switch (circuit breaker)
Filter drier (flare connections)
Sight glass
Crankcase heater
HP/LP adjustable pressostat
Discharge gas thermostat (provision)
HP/LP Alarm (provision)
Installation and servicing of the conden-
sing units by qualified personnel only. Follow
these instructions and sound refrigeration
engineering practice relating to installation,
commissioning, maintenance and service.
The condensing unit must only be used for
its designed purpose(s) and within its scope of
application.
Under all circumstances, the EN378 (or
other applicable local safety regulation)
requirements must be fulfilled.
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
be connected as it is; refer to the «installation»
section for further details.
The condensing unit must be handled with cau-
tion in the vertical position (maximum offset
from the vertical : 15°)
W05
IP54
Scroll/Reciprocating
yes
yes
-
-
yes
yes
yes
Auto/Manual reset mode
yes*
yes*
© Danfoss | Climate Solutions | 2021.07
W09
yes
yes
Tabla de contenido
loading

Tabla de contenido