Application
Thermostat mixers are designed for hot water supply via
pressurised storage heaters and, utilised in this way, provide
the best temperature accuracy. With sufficient power output
(from 18 kW or 250 kcal/min), electric or gas instantaneous
heaters are also suitable.
Thermostats cannot be used in conjunction with
non-pressurised storage heaters (displacement water
heaters).
All thermostats are adjusted in the factory at a flow pressure
of 3 bar on both sides.
Should temperature deviations occur on account of special
installation conditions, the thermostat must be adapted to local
conditions (see Adjusting).
Specifications
Minimum flow pressure without
downstream resistances
Minimum flow pressure with
downstream resistances
Max. operating pressure
Recommended flow pressure
Test pressure
Flow rate at 3 bar flow pressure
Max. water temperature at hot water supply
Recommended max. flow temperature (energy saving) 60 °C
Thermal desinfection possible
Safety stop
Hot water temperature at supply connection min. 2 °C higher
than mixed water temperature
Cold water connection
Hot water connection
Minimum flow rate
If static pressure exceeds 5 bar, a pressure reducing valve
must be fitted.
Installation
Flush piping system prior and after installation of fitting
thoroughly (Consider EN 806)!
Install unions and screw-mount the mixer, see fold-out page II,
Fig. [1].
Refer to the dimensional drawing on fold-out page I.
The projection can be increased by 20mm with an extension,
see Replacement Parts, fold-out page I, Prod. no. 07 130.
Open cold and hot-water supply and check connections
for water-tightness.
Reversed connection (hot on right - cold on left).
Replace thermostatic compact cartridge, see Replacement
parts, fold-out page I, Prod. no.: 47 175 (1/2").
When using this thermostatic compact cartridge, the Cool
Touch function is no longer available.
Adjusting
Temperature adjustment, see fold-out page II Fig. [2].
Temperature end stop
If the temperature end stop is at 43 °C, insert accompanying
temperature limiter in temperature selection handle, see Fig. [3].
Temperature limitation
The safety stop limits the temperature range to 38 °C.
The 38 °C limit can be overridden by pressing the button, see
Fig. [4].
Adjusting the economy stop, see fold-out page II Fig. [5].
If a higher flow rate is desired, the stop can be overridden by
pressing the button, fold-out page II Fig. [6].
Prevention of frost damage
When the domestic water system is drained, thermostat
mixers must be drained separately, since non-return valves
are installed in the hot and cold water connections. For this
purpose, the mixer must be removed from the wall.
Maintenance
Inspect and clean all parts, replace if necessary and lubricate
with special valve grease.
Shut off the hot and cold water supply.
Non-return valve, see fold-out page III, Figs. [7] and [8].
Install in reverse order.
Thermostatic compact cartridge, see fold-out page III,
0.5 bar
Fig. [9].
Install in reverse order.
1 bar
Readjustment is necessary after every maintenance operation
10 bar
on the thermostatic compact cartridge (see Adjusting).
1 - 5 bar
Ceramic headpart, see fold-out page III, Fig. [10].
16 bar
Install in reverse order.
approx. 25 l/min
Replacement parts, see fold-out page I ( * = special
70 °C
accessories).
Care
For directions on care, refer to the accompanying Care
38 °C
Instructions.
right
F
left
= 5 l/min
Consignes de sécurité
Prévention d'échaudage
Pour des points de puisage où la température de
l'eau est particulièrement critique (hôpitaux, écoles,
résidences médicalisées), il est recommandé de
systématiquement utiliser des thermostats pouvant être limités
à 43 °C. Une butée de température permettant la limitation est
incluse avec ce produit. Pour les systèmes de douche dans les
écoles maternelles et dans certaines parties de résidences
médicalisées, il est généralement recommandé de ne pas
dépasser une température de 38 °C. Utilisez ici des
thermostats Grohtherm Special avec poignée spéciale pour
l'aide à la désinfection thermique et la butée finale de sécurité
correspondante. Respectez les normes en vigueur
(par ex. EN 806 2) ainsi que les règlementations techniques
pour l'eau potable.
Domaine d'application
Les robinetteries thermostatiques sont conçues pour fournir de
l'eau chaude avec des accumulateurs sous pression et
permettent d'obtenir une température de l'eau extrêmement
précise. Si la puissance est suffisante (à partir de 18 kW,
ou 250 kcal/min), des chauffe-eau instantanés électriques ou
au gaz conviennent également.
Les thermostats ne peuvent pas être utilisés avec des
accumulateurs sans pression (chauffe-eau à écoulement
libre).
Tous les thermostats sont réglés en usine sur une pression
dynamique de 3 bars. Si des différences de température
devaient apparaître, régler le thermostat en fonction des
conditions locales d'utilisation (voir Réglage).
2
Tabla de contenido
loading

Tabla de contenido