VEK MNE2–R24-F
LED Channel 1
DIP-Switch 1...8
LED Channel 2
DIP-Switch 9...12
Diagnostic (USB)
Reset-Button
1
Characteristic features
11-pole circular connector
Galvanic separation of loop and detector electronics
Automatic system adjustment directly after power-on
Sensitivity adjustment independent of loop inductivity
Loop busy signal emitted by LED-display
Potential-free relay contacts at the outputs
Loop fault message via LED-signal
Indication of historical loop fault
Continuous rebalancing of frequency drifts in order to avoid environmental
influences
Diagnostics by external Service Program via USB-Mini connector
2
Settings
Use the following DIP Switches for the standard settings.
2.1 Sensitivity
DIP 1
DIP 2
Function
DIP 3
DIP4
OFF
OFF
Low
ON
OFF
Medium Low
OFF
ON
Medium High
ON
ON
High
2.2 Frequency
DIP 5
Function
OFF
Low
ON
High
2.3 Hold Time
DIP 6
Function
OFF
5 Minutes
ON
Infinite
2.4 Output Mode Relay 2
DIP 7
Function
OFF
Presence Output on Relay 2
ON
Pulse Output on Relay 2
2.5 Output Edge Relay 2
DIP 8
Function
OFF
Pulse on Loop Entry
ON
Pulse on Loop Exit
2.6 Direction Mode
DIP 9
Function
OFF
Presence Output
ON
Direction sensitive Output
2.7 Direction Logic
DIP 10
Function
OFF
Dir. Logic Presence Output
ON
Dir. Logic Pulse Output
2.8 Fail Save / Fail Secure
DIP 11
Function
DIP 12
OFF
Non Inverted Output Signal
ON
Inverted Output Signal
More settings (Delay, Extension, Loop Fail Output, ..) or more detailed settings
(Sensitivity, Hold Time, Output Modes, ..) can be done via USB Interface with the
Service Program.
VEK MNE2-R24-F
Double-Channel Inductive Loop Detector
DIP 1/2
Loop 1
DIP 3/4
Loop 2
More detailed Sensitivity
settings
via USB Interface!
More detailed Hold Time
settings via USB Interface!
Setting doesn't affect
Relay 1!
Available only if
Relay 2 is in Pulse Output
Mode!
Available only if Direction
Sensitive Output is active!
DIP Switch 11 inverts
output signal on
Relay 1 and DIP Switch 12
on Relay 2.
26.08.2015
Operating Instructions
3
Reset-Button
Press Reset Button 1 s until red LED is flashing to reset/retune detector and clear
historical Loop Fault.
4
LED
Red
Blue
Function
OFF
OFF
No supply voltage
OFF
Fast
Calibration/Retuning Loops
Flashing
OFF
ON
Ready for operation, Loop free
ON
ON
Ready for operation, Loop active
ON
OFF
Loop Fault
x
Flashing
Historical Loop Fault or DIP Switch setting
overwritten by USB*
Blinking
Blinking
Output Loop Frequency in kHz
*) If one or more DIP Switch setting is overwritten by the service program via USB
interface.
Example for loop frequency 57 kHz:
Tens
5x10 kHz
5
Diagnostics
To display more details of the induction loop system, e.g. frequency, detuning, busy
time, output signals, .. use the Service Program on PC.
6
Pin Assignment
Pin
Function
1
Power
+10-30 VDC
2
Power
GND
3
Loop 1
4
Loop 1
5
Loop 2
6
Loop 2
7
Relay 2 N.C.
8
Relay 2 COM
9
-
10
Relay 1 N.C.
11
Relay 1 COM
7
Technical Data
Dimensions (H x W x L)
Power Supply
Operating Temp.
Relays
Loop
Inductivity
Frequency
Supply Line
Resistance
Connectors
Power, Loop, Relay.
Diagnostic
Units
1 s
7x1 kHz
57 kHz
-R24
10-30 VAC
76 x 38 x 71 mm
10-30 V AC/DC, max.1 W
-37 °C...+70 °C
max. 2 A, 50 V AC/DC, 60 W/125 VA
20-700 µH, recommended 100-300 µH
30-130 kHz, 2 steps
max. 200 m
max. 20 Ohm, incl. Loop Supply Line
11-pole circular connector
USB-Mini AB