10.4. ADVANCED SETTINGS

Access to advanced settings after entering code 1234.
22
Door contact activation. With this function and through a door
contact not included (accessory CR-MAGNET COR-PRO), it
will be possible to see on the main screen of the control whe-
ther the door is opened or closed. Unless Automatic Mode A
is active, the curtain will turn off with a delay once the door
closes. The contact is a potential free type and maximum load
is 24VDC/3A.
Door contact position. Function that allows to defi ne door contact as normally open
or closed
.
Run-on-timer when contact disconnection. Once the door contact detects that the door is clo-
sed, it initiates a recommended timing period to dissipate internal heat. It is recommended not
to confi gure a value lower than the factory-set 60s. This function remains active only if the door
contact function has been activated. If automatic mode A is active, this timing is disabled.
Door contact and control valve position. Function only for water coil models.
Keyboard mute.
Keyboard lock to prevent unauthorized manipulation. Once
activated, the keyboard locks after 60 s.
Remote control activation by free voltage contact with maximum load 24VDC/3A. Once active, the
remote control icon on the main screen will appear. If it blinks, it indicates that the contact has
been interrupted.
Automatic A mode activation. Allows automatic operation depending on door contact (accessory).
When door is closed and automatic A mode active, both heating and fans go to minimum levels
as long as reading temperature is higher than set point temperature. Heating system will only
be active when necessary according to measured and required temperature. As long as thermal
support is not needed, fans will remain off. As default into automatic A mode, speed ratio will
respond to: speed 1 if difference between measured and required temperature is less than 2°C;
speed 2 is difference is between 3-5,5°C; speed 3 if between 6-9°C. If icon "A" on the main screen
is illuminated, it indicates that automatic A mode is active. Door contact mode remains active
when this operating mode is activated.
Filter maintenance interval. It allows resetting the countdown for fi lter maintenance (only for
water coil versions)
Heating up mode activation. Pressing icon for 5 seconds activates a mode in which, during selec-
ted time (between 3-15 minutes), air curtain goes to maximum heating and fan speed performan-
ce to force a fast temperature increase. During selected period of maximum performance, if any
button is pressed, the mode is interrupted going to previous confi guration input.