[d] Local shift value weather dependent
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting "[1] Weather
dependent set point" on page 14) is selected.
■ [d-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
L
R
[1-03]
[1-00]
0°C
[1-01]
T
Target water temperature
t
T
Outdoor temperature
A
R Range
L Local shift value
[1-00]~[1-04] Applicable field settings of the weather dependent set
point [1].
Outdoor temperature range
[d-03]
(T
)
A
0
1
–2°C~2°C
2
3
–4°C~4°C
4
[E] Unit information readout
■ [E-00] Readout of the software version (example: 23)
■ [E-01] Readout of the EEPROM version (example: 23)
■ [E-02] Readout of the unit model identification (example: 11)
■ [E-03] Readout of the liquid refrigerant temperature
■ [E-04] Readout of the inlet water temperature
INFORMATION
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated after
looping through the field setting first codes again only.
RKHBH/X008BB
Indoor unit and options for air to water heat pump system
4PW62575-1 – 10.2010
T
A
Local shift value
2
4
2
4
Operation manual