2.0 - TECHNICAL DATA
• Use
• Room temperature (TS)
• Power voltages (see table 3)
• Power supply tolerance
• Electric wiring
• No. of cycles/hour (fast opening valve) :
• No. of cycles/hour (slow opening valve)** :
• Absorbed power
• Maximum operating pressure
• Opening time (fast versions)
• Opening time adjustment (slow versions) : between 0.5 and 40 s ± 20% (Ta= 25 °C - V=Vn)
• Protection rating
• Coil protection mode
• Class
• Mechanical resistance
• Rp threaded fittings
• NPT threaded fittings
• In compliance with
* Only single-phase, the device does not work if powered with three-phase voltage.
** For cycles / hours with ON/OFF times different from those indicated, contact our technical office
2.1 - MODEL IDENTIFICATION
JW-1
: Fast opening
JWF-1 : Fast opening + flow adjustment
JWQ-1 : Adjustable slow opening + adjustable fast stroke
JWR-1 : Adjustable slow opening + flow adjustment
JWS-1 : Adjustable slow opening + adjustable fast stroke + flow adjustment P.max = 0.5 bar
JWT-1 : Adjustable slow opening
2.2 - SIL LEVEL
The SIL level of the stand-alone solenoid valve is SIL 2; when two solenoids are installed in series and the relative seal test
(Valve Proving System), certified according to EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid
valve has PL d level. For further data refer to the SIL LEVEL table (table 2).
3.0 - COMMISSIONING THE DEVICE
3.1 - OPERATIONS PRIOR TO INSTALLATION
All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
• Make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
• In accordance with EN 161 a suitable filter must be installed upstream of a gas closing safety device;
Madas Technical Manual - 1|1.3J - REV. 0 of 1
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60 °C
: 12Vdc - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: electric cable l=3 metres with wire terminals
1800 (ON time 1s - OFF time 1s)
~
210 (ON time 10s - OFF time 7s)
~
: see table 3
: versions with fast opening: 0.5 bar - 1 bar (see product label)
versions with slow opening: 0.5 bar
: <1 s
: IP65
: II 3G Ex mc ec nC IIA T4 Gc X - II 3D Ex mc tc IIIC T135°C Dc X
: A
: Group 2
: (DN 15 - DN 20 - DN 25) according to EN 10226
: request feasibility
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
EN 60079-0-7-14-15-18-31 - ATEX Directive 2014/34/EU
PED Directive 2014/68/EU (versions with P.max = 1 bar)
EMCDirective 2014/30/EU - LVD Directive 2014/35/EU
RoHS II Directive 2011/65/EU
11
Aug 2019
st
P.max = 0.5 bar or 1 bar ATEX 3G - 3D
P.max = 0.5 bar or 1 bar ATEX 3G - 3D
P.max = 0.5 bar
ATEX 3G - 3D
P.max = 0.5 bar
ATEX 3G - 3D
ATEX 3G - 3D
P.max = 0.5 bar
ATEX 3G - 3D
JW...-1