Installation in an L-shaped room
Total area of < 60m²: installation on
the mitre line
Total area of > 60m²: each side is
treated as a separate room
Ceiling beams
In the case of ceiling beams
measuring > 0.2 m and a total area of
< 36 m², detectors should be installed
in the centre of the room either on a
beam or ceiling panel.
In the case of ceiling beams
measuring > 0.2 m and a total area of
> 36 m², detectors should be installed
in the centre of each ceiling panel and
not on the beams.
Mezzanines and landings
In the case of mezzanines and
landings with a length and width of >
2 m and a total area of > 16 m², an
additional smoke alarm should be
installed in the centre of the surface
area.