Cabling
Neutral bus and auxiliary contacts
Cabling / Neutral bus
1
Neutral bus is included/factory mounted in EOH361/2/3NK
-types and optional in EOH361/2/3K -types. Use 5/32 hex
key/wrench. See chapter Installation / Neutral assembly.
Heavy duty fusible safety switch catalog number
AMPS
Suitable neutral bus, catalog number
Neutral bus / terminal lugs
Terminal lug
Torque: wire tightening
Torque: wire tightening
Lug mounting torque
Wire range
Cabling / Auxiliary contacts (optional)
Use Pozi-drive #2 or flat blade screwdriver. See chapter
Installation / Auxiliary contacts (optional).
Auxiliary contacts, catalog numbers OA1G10 (1NO), OA3G01 (1NC)
NEMA
Wire size
Torque
1/8 Cabling | Instruction Bulletin EOH361K/NK, EOH362K/NK, EOH363K/NK, 1SCC340029M1402 / B
A
Copper
lbs.in
Nm
Aluminum
lbs.in
Nm
lbs.in
Nm
AWG
2
mm
A600, R300
1 - 2 × #18 - 14 AWG
1 - 2 × 0.75 - 2.5 mm
2
7 lbs.in
0.78 Nm
EOH361_
EOH362_
30
60
EOHXSN13
EOHXSN13
OZXA100
OZXA100
35
45
3.9
5.1
40
45
4.5
5.1
132
132
14.7
14.7
#14 - 2/0
#14 - 2/0
2.5 - 70
2.5 - 70
EOH363_
100
EOHXSN13
OZXA100
50
5.6
50
5.6
132
14.7
#14 - 2/0
2.5 - 70