guarantee the electric lock or mechanical bolt coupling.
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in gate
opening and in gate closing. In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle
is removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in gate
closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a
close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers
must be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire
jump (from PHOT to COM) to permit the gate to operate.
ATTENTION: In case the receiver led remains lit,
malfunctioning of the main supply is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal A -,
to shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
AUTOMATIC CLOSING AFTER THE TRANSIT THROUGH THE PHOTOCELL
DIP12 ON and DIP4 OFF =>
If the gate is opening and a vehicle crosses the photo
beam, the gate will stop. When the vehicle leaves, the
gate will close automatically after 1 second pause.
DIP12 ON and DIP4 ON =>
If the gate is opening and a vehicle crosses the photo
beam, the gate will continue to open. When the vehicle
leaves, the gate will stop and then closes automatically
after 1 second pause.
DIP 12 ON and DIP 3 ON => (Automatic closing activated), when passing
through the gate in open position, as soon as the beam
of the photocells is cut and released, the closing of the
gate will activate immediately.
DIP 12 ON and DIP 3 OFF => (Automatic closing disabled), when passing through
the gate in open position, even if the beam of the
photocells is cut and released, the gate will remain
opened.
DIP 12 OFF => immediate closure after transit from the photocells disabled.
PAY ATTENTION: it is highly recommended to check photocells operation at least every
6 months.
SAFETY STRIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is
performed. The gate interrupts any movement and this alarm state is indicated by 1
minute Blinker flashing. The normal gate operations can be restored by pressing any
push button or radio commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact.
In case there are more than one safety strip, all their contacts must be connected in
series.
In case the safety strip is not installed, this contact must be short circuited with
a wire jump (from EDGE to COM) to permit the gate to operate and the Safety
Strip test must be disabled (DIP 13 OFF).
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or
remain engaded for more than 60 seconds, the K BUTTON and PEDESTRIAN commands
will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming
led.
With the blinking of the programming led, the opening and closing operation are allowed
only with the command button pressed and held. The radio commands and that of
automatic closing, will be excluded, since their use in this mode, is not allowed by the
norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio commands
and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety
During the dead-man operation, press and hold the K BUTTON or the PED BUTTON for
the complete operation, and until the switching off of the leds of the motors (DL3 - DL5
total opening M2 - M1 - pedestrian DL5 - DL4 - DL6 total closing M2 - M1 - pedestrian
DL6), or of the blinker, when installed.
The dead-man operation is only an emergency operation which must be
activated for a very short period and with the complete installation at sight so
to have a secure and safe control of the system. As soon as possible however,
the failing safety devices must be repaired and activated.
24Vdc
TESTING THE SAFETY STRIP equipment
Term.
The switch DIP13 ON enables to test the safety strip equipment. The test is performed
A -
every time the gate completes a full opening. The test is available only if the safety
strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the A+TEST
and A - outputs (DIP13 ON). Automatically, every time the gate completes a full opening,
just before closing, the control board switches OFF the A+TEST and A - power supply
output for a very short time. While the safety strip power supply is switched OFF, if
everything is working fine the safety strip contact (EDGE - COM) must open. In case the
test fails, no other gate manoeuvre will be allowed.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP13 MUST BE
LEFT OPEN.
BLINKER
Connect the flashing light to the blinker output, use flashing lights ACG7059 and bulbs
of 40W maximum.
PRE-FLASHING function
The DIP 5 in the ON position enables the pre-flashing, the BLINKER starts flashing 3
seconds before every movement of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the BLINKER starts flashing and
the motors will start at the same time.
BUZZER
The current supplied to the Buzzer will be 200 mA at 24Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz
intermittently. Only during the alarm situations (safety strip) the buzzing will almost be
constant.
GATE OPEN INDICATOR (SIGNAL - COM)
Should you need to have an indication about the leaf position, the output SIGNAL - COM
can be connected to a 24Vdc bulb of 3W maximum. It is turned ON when the gate is open
or partially open, it is turned OFF only when the gate is completely closed.
WE RECOMMEND NOT TO OVERLOAD THE INDICATOR OUTPUT (SIGNAL - COM)
OTHERWISE THE GATE FUNCTIONING COULD BE COMPROMISED OR THE CONTROL
BOARD COULD BE DAMAGED
RESTORATION OF OPERATIONS AFTER A BLACKOUT
If DIP 11 is turned OFF the blackout function is DISABLED.
If DIP 11 is turned ON the blackout function is ENABLED.
In case of a blackout occurs and the blackout function is enabled (DIP11 ON), when the
main power returns, automatically the operator will function according to the chart 1.
33
strips (or photocells) the photocells (or safety strips) still work by interrupting the
operation in progress.