Power Source Installation - Haier HSM07HEA03/R2 Manual De Instalación

Ocultar thumbs Ver también para HSM07HEA03/R2:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

All manuals and user guides at all-guides.com

1.Power Source Installation

The power source must be exclusively used for air conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place, please install an
earth leakage breaker.
For installation in other places, use a circuit breaker as far as possible.
2.Cutting and Flaring Work of Piping
Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.
A
Flare tooling die
1.Cut pipe
3.Insert the flare nut
4.Flare pipe
3.On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.
The end is immersed
It becomes high midway.
in water.
Please pour water in the drain pan of the indoor unit, and confirm that drainage is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation
to it without fail.
Check for Installation and Test Run
Please kindly explain to our customers how to operate through the instruction manual.
Check Items for Test Run
Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of
indoor and outdoor firmly inserted
to the terminal block?
Is the connecting wiring of indoor
and outdoor firmly fixed?
Flare tool for R410A
Clutch-type
2.Remove burs
Correct
It waves.
Put check mark
in boxes
Is drainage securely carried out?
Is the earth line securely
connected?
Is the indoor unit securely fixed?
Is power source voltage abided
by the code?
Is there any noise?
8
Conventional flare tool
clutch-type(Rigid-type) Wing-nut type (Imperial-type)
0~0.5mm
1.0~1.5mm
Incorrect
Lean Damage of flare Crack
Less than 5cm
The gap with the ground
There is the bad smell
is too small
from a ditch
Is the lamp normally lighting?
Are cooling and heating (when
in heat pump) performed normally?
Is the operation of room temperature
regulator normal?
1.5~2.0mm
Partial Too outside
Tabla de contenido
loading

Este manual también es adecuado para:

Hsm09hea03/r2Hsm12hea03/r23hum20ha03/r2Hsm07hea03/r2 dbHsm09hea03/r2 dbHsm12hea03/r2 db ... Mostrar todo

Tabla de contenido