1-10
Instalación/Cableado
Figura 1.3 Ubicación Típica del Bloque de Terminales de Potencia
➌
!
DANGER
Use 75C Wire Only
#10-#14 AWG
Torque to 7 in-lbs
BR1
➌
BR2
DC+
DC–
PE
U/T1
V/T2
W/T3
R/L1
S/L2
➊
T/L3
➋
Bastidores 0 y 1
➋
POWER TERMINAL RATINGS
2
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75° C CU WIRE ONLY
17
GROUND TERMINAL RATINGS (PE)
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
21
➌
OUTPUT
➊
Bastidor 5
Optional
Communications
Module
BR1 B
V/T2 W/T3
AUX IN+ AUX OUT–
SHLD
➊
Bastidor 2
Optional
Communications
Module
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
9
INPUT AC
Sólo variadores
con bus común
WIRE
STRIP
75C Cu Wire
2
6 AWG [10MM
] Max.
12 IN. LBS.
} TORQUE
1.4 N-M
PE R/L1 S/L2 T/L3
➊
SHLD
➌
➋
PE
/
SHLD
➋
➋
Communications
➌
22-10
AWG
BR2
BR1
5.3 IN-LB
(0.6 N-M)
USE 75°C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
➊
USE 75°C
COPPER WIRE
ONLY
TORQUE
T1
T2
52 IN-LB
OUTPUT
(6 N-M)
➍
Optional
Communications
Module
PE B
PE A
WIRE
STRIP
BR1 BR2
75C Cu Wire
75C Cu Wire
6 AWG [10MM 2 ] Max.
2
3 AWG [25MM
] Max.
12 IN. LBS.
16 IN. LBS.
} TORQUE
} TORQUE
1.4 N-M
1.8 N-M
AUX IN
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3
+
–
PE
SHLD
Bastidores 3 y 4
Optional
Module
DC+
DC–
T3
L1
L2
L3
INPUT
Bastidor 6