6.0 TECHNICAL DATA

MODEL
DEHUMIDIFICATION
TOTAL HEAT TO AIR:
DEHUMIDIFIER ONLY
DEHUMIDIFIER & LPHW
LPHW ONLY
NOMINAL POWER CONSUMED:-
FAN ONLY
DEHUM' (COMP & FAN)
SUPPLY
FUSE
NOMINAL RUNNING AMPS
FULL LOAD AMPS
COMPRESSOR L.R.A.
AIR FLOW
NOISE LEVEL @ 3m
LPHW FLOW RATE
LPHW PRESSURE DROP
LPHW VOLUME
REFRIGERANT CHARGE
IP RATING
WEIGHT UNPACKED/PACKED
a) These performance figures are based on air @ 30ºC, 60% RH and boiler water @ 80ºC
b) Humidistat adjustable from 20% to 80%
c) Minimum air temperature on standard (A) models 15°C
d) Minimum air temperature on defrost (AX) models 5°C
e) Maximum operating conditions air temp 35ºC and 90% RH
1L/min=0.22gall/min
1m hd =1.4psi
1mm Wg =9.8Pa
All manuals and user guides at all-guides.com
l/hr
l/day
kW
kW
kW
kW
kW
AMP
AMP
AMP
AMP
m³/h
dB/A
l/min
m hd
l
kg R407c
kg
Page 13
DH44A/AX
DH66A/AX
1.25
2.41
30.0
58.0
1.6
3.0
4.9
8.8
3.3
5.8
0.04
0.07
0.51
0.98
230V 50Hz
230V 50Hz
10
13
2.6
4.2
3.5
6.0
12.0
26.0
440
740
42
44
4.8
10.2
3.8
3.4
0.9
1.4
1.1
1.7
45
45
57/81
74/106