Velleman EMDIN03 Manual De Funcionamiento página 4

Ocultar thumbs Ver también para EMDIN03:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
display mode
power consumption
temperature range
max. operating altitude
LED indicator
pulse output
(1)
3x5(100)A: 3x5 → (Ib = 5 A) and (100) → I max = 100 A.
The internal measurement always happens at 3x5 A (Ib) (5A
per phase), this via an internal voltage divider. For example, a
live current of 25 or 32 A flows through the circuit. The max
current for this kwh meter may be 100 A (I max) per phase.
Note: the most accurate measurement for these kWh meter, is
by a live current of 5 A through the circuit.
Use this device with original accessories only. Velleman Group
nv cannot be held responsible in the event of damage or
injury resulting from (incorrect) use of this device. For more
info concerning this product and the latest version of this
manual, please visit our website www.velleman.eu. The
information in this manual is subject to change without prior
notice.
© COPYRIGHT NOTICE
The copyright to this manual is owned by Velleman Group nv.
All worldwide rights reserved. No part of this manual may be
copied, reproduced, translated or reduced to any electronic medium
or otherwise without the prior written consent of the copyright
holder.
V. 08 – 04/01/2022
EMDIN03
LCD 6+1 = 999999.9 kWh
≤ 2 W (10 VA)
-20 to 55 °C
2000 m
1 blink per pulse
800 imp/kWh
voltage: 12 to 27 V
current: 27 mA
impulse width: 90 ms
4
©Velleman Group nv
Tabla de contenido
loading

Tabla de contenido