Setting the Extended Charging Parameters
By pressing the button „Ser ice for a longer period of time further charging parameters can be set or
retrieved.
De-Sulphating on/off (only wet type batteries)
Adaptation of the end-of-charge voltage (Gassing voltage) in a given range (for 12 V batteries
only)
Language
Software-Version
Illustration 6: Display in extended "Service"-Menu
Start charging (with I-Check)
1. Connect the charger to the mains
2. Adapt the charging parameters to the battery to be charged
3. Connect the battery to the charger
4. Charging will start automatically
5. In the beginning of the charging process the ability for current drain (I-check) of the battery will
be tested.
The battery voltage will be checked during this I-check and must exceed 1.5 volts / cell after 30 minutes to
pass the test. The charge will continue automatically. In the other case, a time error is output. If the battery
voltage is between 0.5 volts / cell and 1.5 volts / cell, it is automatically tested with a reduced current (10%
of I
).
rated
Illustration 7: Display during Charging
8
EN
Illustration 8: Display during De-Sulphating Charge
Charge Mode