2.9 Additional safety instructions
CAUTION
3RB22 / 3RB24 and 3RB29 are not designed for use in hazardous
areas. When used in potentially explosive areas, 3RB22 / 3RB24
and 3RB29 devices must be adapted according to the respective
ignition protection type.
The 3RB22 / 3RB24 is not designed for load-side operation at
frequency converters.
NOTICE
Brief power failures (voltage drops) < 150 ms at the 3RB22 do not
lead to a protective system failure.
Long power failures (voltage drops) > 150 ms at the 3RB22 cause
the output relays to be deactivated.
NOTICE
Brief power failures (voltage drops) < 89 ms at the 3RB24 do not
lead to a protective system failure.
Long power failures (voltage drops) > 89 ms at the 3RB24 cause
the output relays to be deactivated.
2.10 Ambient conditions
Permissible ambient temperature range
• Storage / transport: -40 °C to +80 °C
• Operation:
-25 °C to +60 °C
3. Safety data 3RB22 / 3RB24
SIL
HFT
λ
safe
λ
DD
λ
DU
SFF
DC
MTBF:
PFD
avg (36 Months)
Architektur
T1-Wert
(periodic inspection)
T
Iifetime
4. Maintenance and repair
This device is maintenance-free.
5. Warranty
The warranty implies the observance of these safety and commission-
ing instructions as well as the operating instructions (order No.
3ZX1012-0RB22-1AA1 (3RB22), 3ZX1012-0RB24-1AA1 (3RB24) and
order No. 3ZX1012-0RB00-1AA1 (3RB29).
6. Further information
Further information on the 3RB22 / 3RB24 / 3RB29 device can be
found in the Siemens IC 10 catalog or on the Internet:
https://support.industry.siemens.com/
6
Values in the safety and
commissioning notes for 40°C
ambient temperature
3RB22
3RB24
SIL 1
0
1232
1458
Fit
433
661
Fit
382
264
Fit
81,1
88,9
%
53,1
71,5
%
55
47
Yearths
-3
-3
8,2 10
5,7 10
1oo1
36
Months
20
Years
3ZX1012-0RB22-1CA1