PanelView 550 Terminals
Connecting AC Power
The table below shows the electrical ratings for the AC versions of the terminals .
Terminal Type
PV550
ATTENTION
!
ATTENTION
!
To connect AC power to the PanelView 550 terminals:
1. Secure the AC power wires to the L1 and L2N terminal block screws.
2. Secure the Earth Ground/Protective Earth wire to the GND screw on the
terminal block.
ATTENTION
!
40061-325-01(D)
Supply Voltage
85 to 264V ac, 47 to 63 Hz
• The PanelView 550 terminal is designed for safe use when
installed in a suitably rated NEMA Type 12, 13, 4X (indoor
use only), IP54 or IP65 enclosure.
• Do not apply power to the terminal until all wiring
connections have been made. Failure to do so may result in
electrical shock.
Explosion Hazard - Do not connect or disconnect equipment
while circuit is live unless area is known to be non-hazardous.
Improper wiring of the power terminals may result in
voltage at the communication connector shells. Refer to the
following figure when wiring.
Power Consumption
45 VA maximum