Technical specifications | RAR200 A without heat 1
Type
Output
[kW]
RAR210A
0
RAR215A
0
0
RAR220A
Technical specifications | RAR200 E electrically heated 3
Type
Output
Output
steps
steps
400V3N~
230V~
[kW]
[kW]
RAR210E09 3
-
6/9
-
-
3
-
3/5
RAR215E11 4,5
-
6,8/11,3
-
-
4,5
-
4,5/6,8
RAR220E18 6
-
12/18
-
-
6
-
6/10
Technical specifications | RAR200 W water heated
Type
Output*³
Airflow
[kW]
[m
RAR210W 6,6
700/1000
RAR215W 10,4
1000/1600 37/50
RAR220W 13,0
1400/2000 44/53
*1) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m².
At lowest/highest airflow.
*2) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*3) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
RAR200E is delivered as 9 kW, 11 kW and 18 kW (400V3N~) models, but they are convertible to 230V~ and
different outputs as shown in above table.
Protection class RAR200A/E/W: normal design (IP20).
CE compliant.
Airflow
Sound level*¹
[m
/h]
[dB(A)]
3
650/1200
34/50
950/1750
34/50
1300/2400
40/54
Airflow
Sound
level*¹
[m
/h]
[dB(A)]
3
650/1200 34/50
650/1200 34/50
650/1200 34/50
650/1200 34/50
950/1750 34/50
950/1750 34/50
950/1750 34/50
950/1750 34/50
1300/2400 40/54
1300/2400 40/54
1300/2400 40/54
1300/2400 40/54
∆t*
Sound
2,3
level*
1
/h]
[dB(A)]
3
[°C]
41/49
24/21
24/20
23/20
Voltage
Amperage
[V]
[A]
230V~
0,5
230V~
0,6
230V~
1,0
∆t*
Voltage
Amperage
2
400V3N~
[°C]
[V]
[A]
13/7
400V3N~ 4,3
41/22
400V3N~ 13
13/7
230V~
-
23/12
230V~
-
14/8
400V3N~ 6,5
35/20
400V3N~ 16
14/8
230V~
-
21/12
230V~
-
13/7
400V3N~ 8,7
41/22
400V3N~ 26
13/7
230V~
-
23/12
230V~
-
2
Watervolume
Voltage
[l]
[V]
0,5
230V~
0,9
230V~
1,1
230V~
RAR 200 A/E/W
Length
Weight
[mm]
[kg]
1042
18
1552
25
2042
36
Amperage
Length
230V~
[A]
[mm]
-
1042
-
1042
13
1042
22
1042
-
1552
-
1552
20
1552
30
1552
-
2042
-
2042
26
2042
43
2042
Amperage
Length
Weight
[A]
[mm]
[kg]
0,4
1042
21
0,6
1552
39
1,0
2042
42
Weight
[kg]
23
23
23
23
32
32
32
32
44
44
44
44
15