Setting Sensitivity
This setting is affected by the dampness and surface bonding strength of the
material. The sensitivity should be set to 10% in wet bulk material that has a strong
tendency to cake or deposit and adjusted to 50% or 60%, in case of very dry and
low specific weights.
For example; the most effective sensitivity varies between 30% to 40%, in case of
bulk materials such as lime, plaster, cement, powdery paints, pulverised coal and
etc., depending on the level of dampness.
Mode of Operation and Warnings
Vibrates continuously at 80 Hz in idle position. Once the bulk material to be detected
covers the probe, it shall pull off the output relay in no later than 1.0 sec. It should
not be used singly at a check point where human lives can be endangered. At check
points where a high level of safety is required, multiple point checks should be
performed with mounting of more than one switches at the same measurement
level. The manufacturer is not responsible for casualties and damage that may
occur as a result of erroneous detections.

Ordering Codes

The only model currently available for sale is VBR0320-24VDC 24V supply version.
Legal Compliance
CE conformance
EN 61000-6-4:2001 Generic emission standard. Industrial environments.
EN 61000-6-2:2005 Generic emission standard. Industrial environment.
EN 61010-1:2001 Safety requirements for electrical equipment for measurement,
control, and laboratory use.