Energi Savr Node
Step 2: Mains voltage wiring
The Energi Savr NodeT with EcoSystemR unit operates at
220-240 V~. Use the following instructions to wire line voltage
to the Energi Savr NodeT with EcoSystemR unit.
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power via circuit breaker before wiring or servicing
the Energi Savr NodeT with EcoSystemR unit.
Buttons and LEDs on the front of the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
1. Turn power off.
2. Use 1,0 mm
to 4,0 mm
conductors (depending on breaker
2
2
rating) to feed the mains wiring. The device draws less than
100 mA.
3. Strip 8 mm of insulation off the mains cables.
4. Wire the mains to the terminals labelled L, N, and .
A three-position terminal block is provided. Do not wire L or N
wires to the
terminal.
5. The recommended installation torque is 0,5 N·m
6. The Energi Savr NodeT with EcoSystemR unit is earthed
through the
terminal. Attach the earth wire.
7. Close front cover of panel.
8. Turn on the circuit breaker to power up the Energi Savr NodeT
with EcoSystemR unit. The POWER indicator on the Energi
Savr NodeT with EcoSystemR unit will display a green light
continuously when properly powered up. If the indicator does
not light, turn off power, then check the mains voltage wiring
and repeat this step.
9. Turn power off.
Note: If additional wiring space is required, the Energi Savr
NodeT with EcoSystemR unit can be removed from the DIN rail
while wiring. Follow the instructions in Step 1: Mounting the
Energi Savr NodeT with EcoSystemR unit on page 3.
Lutron
4
|
®
with EcoSystemR
TM
International Energi Savr Node
|
Installation Guide
L N
with EcoSystemR Installation Guide
TM
Mains Wiring:
• 1,0 mm
to 4,0 mm
2
2
• Strip length: 8,0 mm
• Torque: 0,5 N
m
•