Connection
Plug your UPS's Line Cord into
1
an electrical outlet.
Once your UPS is plugged in, the UPS will enter STANDBY
mode. The fan will activate and the "
begin flashing. The UPS system's outlets will not be
active until the UPS is turned ON.
SMART1400RM2U and SMART1500RMXL2U
models require connection to a 15-amp dedicated circuit.
SMART2200RMXL2U and SMART2600RM2U models
are fitted with plugs for connection to a 20-amp dedicated
circuit, but may be reconfigured for use with a 15-amp
dedicated circuit (see "Switching Plugs" below).
SMART3000RM2U models are fitted with twist-lock
plugs for connection to a 30-amp dedicated circuit, but
may be reconfigured for use with a 20-amp dedicated
circuit (see "Switching Plugs" below).
Switching Plugs: Plug switching should only be done
by a qualified electrician. Switching plugs will change
the output capacity of your UPS; see Specifications.
Plug your equipment into your UPS.
2
Your UPS is designed to support only computer equipment.
You will overload your UPS if you connect household
appliances, laser printers or surge suppressors to the
UPS's Outlets.
Turn your UPS ON
3
• Press the "POWER" button
• Hold the button for a moment, until the "
LED stops flashing and illuminates constantly
• Release the button
Your UPS is now ON and its AC outlets are active.
" LED will
1
2
"
3
6
SMART2200RMXL2U plug
(NEMA 5-20P) shown
SMART3000RM2U shown