Main Components - Galletti FLAT S Serie Instalación Uso Y Mantenimiento

Ventiloconvectores compactos de diseño con ventilador centrífugo
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
FLAT S

MAIN COMPONENTS

Cabinet
RAL9010 colour, front panel made
of sheet steel. Side panels and
an upper grille with covers on
either side manufactured from
UV-stabilised ABS to maintain
the colour intact over time. The
EN
upper grille consists of a flap and
adjustable louvers. The flap features
a microswitch that automatically
shuts down the unit when the flap
itself is closed.
Fans
Double suction centrifugal
fans, statically and dynamically
balanced, manufactured from
anti-static ABS, with blades
having an airfoil section and
offset modules. The fans are
housed in a low-noise ABS volute
with high-efficiency profile.
ACCESSORIES
Electromechanical control panels
Electromechanical controller, complete with speed selector,
TIB
thermostat and summer/winter selecting switch
Electromechanical thermostat for minimum water temperature in
TC
heating mode, mounted on the heat exchanger
CD
Recess wall-mounted speed selector
CDE
Wall-mounted speed selector
Wall-mounted electromechanical controller, complete with speed
TD
selector, thermostat and summer/winter selecting switch.
Wall-mounted electromechanical controller, complete with speed
TDC
selector and thermostat.
Wall-mounted electromechanical controller, complete with speed
TD4T
selector, thermostat and summer/winter selecting switch for
control of the fan coil and ON/OFF valves.
Wall-mounted microprocessor electronic control panels
MCBE
MYCOMFORT BASE electronic controller with display
MCME
MYCOMFORT MEDIUM electronic controller with display
MCLE
MYCOMFORT LARGE electronic controller with display
EVO
Wall-mounted and on-board mounted microprocessor controller
KBFLAE
FLAT on-board installation kit
Water probe for microprocessor controls model MYCOMFORT
MCSWE
BASE, MEDIUM, LARGE and EVO
FC66004073- 00
FC66004073- 00
Electric motor
It is mounted on vibration dampers, with permanently activated capacitor
and thermal protection of the windings, and is directly coupled with the fans.
It is available as 3-speed version in order to meet all the specific needs of
performance, quietness, and power consumption.
All copying, even partial, of this manual is strictly forbidden
Structure
Built from galvanised steel sheet
of extra thickness, heat and
sound insulated by means of
Class 1 self-extinguishing panels.
Remote humidity sensor for EVO, MYCOMFORT MEDIUM and
MCSUE
LARGE on-board controllers
Power interface
Power interface for connecting in parallel up to 4 fan coils to one
KP
controller
Additional heat exchanger for 4-pipe systems
1 row additional heat exchanger for 4-pipe systems (hot water
DFS
circuit)
Base supports and enclosing panels
ZLS
Pair of base and enclosure elements
Rear pre-painted panel for vertical installation fan coils with
PVS
cabinet
Valves
2 or 3-way valve with ON/OFF or modulating electrothermal motor
VKS
and hydraulic kit for standard heat exchanger
2 or 3-way valve with ON/OFF or modulating electrothermal motor
VKDFS
and hydraulic kit for DF heat exchanger
Auxiliary water drip trays, insulating shell
BV
Auxiliary water drip tray for vertical installation fan coil units
GIVKS
Valve insulation shell
10
Heat exchanger
High efficiency heat exchanger
made with copper piping and
aluminium fins, provided with
brass manifolds and vent
valve. The water connections
are reversible at the time of
installation. On request it is
possible to mount an additional
heat exchanger for 4-pipe
systems.
Air filter
Honey-comb polypropylene
washable air filter, easily
removable for maintenance
operations.