SMA SUNNY TRIPOWER 5.0 SMART ENERGY Instrucciones Breves página 9

Ocultar thumbs Ver también para SUNNY TRIPOWER 5.0 SMART ENERGY:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 73
SMA Solar Technology AG
Danger to life due to fire and explosion
In rare cases, an explosive gas mixture can be generated inside the product under fault
conditions. In this state, switching operations can cause a fire inside the product or explosion.
Death or lethal injuries due to hot or flying debris can result.
• In the event of a fault, do not perform any direct actions on the product.
• Ensure that unauthorized persons have no access to the product.
• Do not operate the DC load-break switch on the inverter in case of an error.
• Disconnect the PV array from the inverter via an external disconnection device. If there is no
disconnecting device present, wait until no more DC power is applied to the inverter.
• Disconnect the battery from the product via an external disconnection device. Do not
operate the DC load-break switch on the product.
• Disconnect the AC circuit breaker, or keep it disconnected in case it has already tripped,
and secure it against reconnection.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
Risk of injury due to toxic substances, gases and dusts.
In rare cases, damages to electronic components can result in the formation of toxic substances,
gases or dusts inside the product. Touching toxic substances and inhaling toxic gases and dusts
can cause skin irritation, burns or poisoning, trouble breathing and nausea.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
• Ensure that unauthorized persons have no access to the product.
Danger to life due to fire or explosion when batteries are fully discharged
A fire may occur due to incorrect charging of fully discharged batteries. This can result in death
or serious injury.
• Before commissioning the system, verify that the battery is not fully discharged.
• Do not commission the system if the battery is fully discharged.
• If the battery is fully discharged, contact the battery manufacturer for further proceedings.
• Only charge fully discharged batteries as instructed by the battery manufacturer.
Quick Reference Guide
WARNING
WARNING
WARNING
STPx.0-3SE-40-IS-xx-12
2 Safety
9

Hide quick links:

Tabla de contenido
loading

Tabla de contenido