Instructions
itself is not a "unit" in the scope this directive.
• It is recommended to install the unit on rubber
grommets or vibration dampers (not supplied).
• It is possible to stack units on top of each other.
Unit
Housing 1
(Code no. 114X31-- or 114X41--)
Housing 2
(Code no. 114X32-- or 114X42--)
Housing 3
(Code no. 114X33-- or 114X43--)
Housing 4
(Code no. 114X34-- or 114X44--)
• When stacking, the topmost unit must be secu-
red to the wall, as shown in picture 2.
• Slowly release the nitrogen holding charge
through the schrader port.
• Connect the unit to the system as soon as pos-
sible to avoid oil contamination from ambient
moisture.
• Avoid material entering into the system while
cutting tubes. Never drill holes where burrs
cannot be removed.
• Braze with great care using state-of-the-art
technique and vent piping with nitrogen gas
flow.
• Connect the required safety and control de-
vices. When the schrader port is used for this,
remove the internal valve.
• It is recommended to insulate the suction pipe
up to the compressor inlet with 19 mm thick
insulation.
5 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosion.
• Do not use dye for leak detection.
• Perform a leak detection test on the complete
system.
• The maximum test pressure is 31*
• When a leak is discovered, repair the leak and
repeat the leak detection.
*
)
25 bar for OP-.......AJ.... & OP-.......FH.... models
6 – Vacuum dehydration
• Never use the compressor to evacuate the sys-
tem.
• Connect a vacuum pump to both the LP & HP
sides.
• Pull down the system under a vacuum of 500
µm Hg (0.67 mbar) absolute.
• Do not use a megohmmeter nor apply power
to the compressor while it is under vacuum as
this may cause internal damage.
7 – Electrical connections
• Switch off and isolate the main power supply.
• Ensure that power supply can not be switched
on during installation.
• All electrical components must be selected as
per local standards and unit requirements.
• Refer to wiring diagram for electrical connec-
4 | AN18658643414604-001401 - 118U3276C
tions details.
• Ensure that the power supply corresponds to
the unit characteristics and that the power sup-
ply is stable (nominal voltage ±10% and nomi-
nal frequency ±2,5 Hz).
Maximum
stacking
• Dimension the power supply cables according
to unit data for voltage and current.
3
• Protect the power supply and ensure correct
2
earthing.
• Make the power supply according to local stan-
2
dards and legal requirements.
• The unit is equipped with an electronic control-
2
ler. Refer to Manual RS8GDxxx for details.
• P02 version models (OP-xxxxxxxxxP02E) are
equipped with Electronic circuit board (Module
B Plus). Refer to section " Module B Plus User
Guide " of this manual.
• The unit is equipped with a main switch with
overload protection. The overload protection is
factory preset but it is recommended to check
the value before taking the unit in operation.
The value for the overload protection can be
found in the wiring diagram in the front door of
the unit.
• The unit is equipped with high and low pres-
sure switches, which directly cut the power
supply to the compressor in case of activation.
Parameters for high and low pressure cut outs
are preset in the controller, adapted to the com-
pressor installed in the unit.
• P05 models are also equipped with phase
sequence relay to protect the unit against
phase loss/sequence/ asymmetry and under-/
over-voltage.
For units with a 3-phase scroll compressor (OP-
MPXMxxxxxxxxE), correct phase sequence for
compressor rotation direction shall be observed.
• Determine the phase sequence by using a
phase meter in order to establish the phase
)
bar.
orders of line phases L1, L2 and L3.
• Connect line phases L1, L2 and L3 to main swit-
ch terminals T1, T2 and T3 respectively.
8 – Safety
Fusible Plug is not installed in unit, it is replaced
with adapter blanking plug.
Unit has liquid receiver with an Adapter Plug with
3/8" NPT connection. installer/end user can select
various options as mentioned in EN378-2 : 2016
Article § 6.2.2.3
• The unit/installation into which the condensing
unit is mounted/integrated, must be in accor-
dance with the PED.
• Beware of extremely hot and cold components.
• Beware of moving components. Power supply
should be disconnected while servicing.
9 – Filling the system
• Never start the compressor under vacuum.
Keep the compressor switched off.
• Use only the refrigerant for which the unit is
designed for.
• Fill the refrigerant in liquid phase into the
condenser or liquid receiver. Ensure a slow
charging of the system to 4 – 5 bar for R404A/
R448A/R449A/R407A/R407F/R452A and ap-
prox. 2 bar for R134a and R513A.
• The remaining charge is done until the instal-
lation has reached a level of stable nominal
condition during operation.
• Never leave the filling cylinder connected to
the circuit.
10 – Setting the electronic controller
• The unit is equipped with an electronic control-
ler which is factory programmed with parame-
ters for use with the actual unit. Refer to Manual
RS8GDxxx for details.
• By default, the electronic controller display
shows the temperature value for the suction
pressure in °C. To show the temperature value for
the condensing pressure, push the lower button
(picture 3).
The electronic controller is factory preset for R404A
or R449A or R452A or R134a depending on the mo-
del of compressor mounted and application (Refer
Annexx in Optyma Controller installation manual).
If another refrigerant is used, the refrigerant setting
must be changed. Parameter r12 must be set to 0
before (software main switch= off).
• Push the upper button for a couple of seconds.
The column with parameter codes appears.
• Push the upper or lower button to find parame-
ter code o30.
• Push the middle button until the value for this
parameter is shown.
• Push the upper or lower button to select the new
value: 2 = R22, 3 = R134a, 36 = R513A, 17 = R507,
19 = R404A, 20 = R407C , 21 = R407A, 37 = R407F,
40 = R448A, 41 = R449A, 42 = R452A.
• Push the middle button to confirm the selected
value.
For P02 version models (OP-xxxxxxxxxP02E),
if o30 value is 19= R404A or 40=R448A or
41=R449A in controller,
• Push the upper or lower button to find parame-
ter code r84.
• Push the middle button until the value for this
parameter is shown as 125
• Push the upper button to select the new value:
130.
Change controller parameter o37 to 1 in
case of SPPR retrofit. In case you add the SPPR
(Supply monitoring relay) option to protect
the compressor please change the setting O37
from 0 to 1
11 – Verification before commissioning
Use safety devices such as safety pressure swit-
ch and mechanical relief valve in compliance with
both generally and locally applicable regulations
and safety standards. Ensure that they are opera-
tional and properly set.
Check that the settings of high-pressure swit-
© Danfoss | DCS (CC) | 2020.06