Installation Instructions
Occupant Copy
Features
QSE-IO
• Integrates a GRAFIK Eye QS lighting control system with
equipment that has contact-closure I/O, including:
- Motion and occupant sensors.
- Timeclocks and push buttons.
- Motorized projection screens, skylights, window shades, and
movable walls.
- AV equipment.
- Security systems.
• May be programmed to control or be controlled by any
combination of GRAFIK Eye QS control units, or control any
combination of Sivoia
QS shades on the link.
®
Inputs/Outputs:
• Provides five inputs and five outputs.
• Provides both normally open (NO) and normally closed
(NC) contacts.
• Using the inputs, contact closures in other equipment can operate
control units to:
– Select scenes.
– Adjust scenes to reflect status of movable walls.
– Toggle any combination of zones in the system between Off and
a configurable preset value.
– Turn lights on or off based on room occupancy.
– Perform special functions such as sequencing, panic, control
lockout, or timeclock disable.
• Using the outputs, scene changes in control units can:
– Trigger outputs to control other equipment.
– Provide status feedback to other equipment.
• Using the inputs, contact closures in other equipment can operate
Sivoia QS shades to:
– Open or close.
– Raise, lower, or stop.
– Select one of three adjustable presets.
• Using the outputs, key presses on QS shade keypads or
GRAFIK Eye QS shade column buttons can:
– Trigger outputs to other motorized shade equipment.
Seven Types of Configuration:
1. Scene Selection Control: Provides for remote control of
GRAFIK Eye QS control units. Can be used to select any group of
four scenes and send the system to the Off scene.
Maintain Outputs: Allows the selection of up to 5 contact
closures to other manufacturers' A/V equipment.
Momentary Outputs: Allows the selection of other manufacturers'
equipment, such as projection screens, requiring momentary
output closures.
2. Zone Toggle Control: Provides for independent toggling of up
to 5 GRAFIK Eye QS zones or groups of zones between Off and
an adjustable preset value. Zone toggle with raise/lower provides
up to 3 zone toggles, in addition to raise/lower control of the last
zone(s) toggled.
®
Please Read
QSE-IO Control Interface
PELV (Class 2: USA) Device 24 V
3. Special Function Control
Sequencing: Cycles the preset light levels from scene 5 through
16 and back to scene 5, looping indefinitely and using the
programmed fade times for each scene.
Zone Lockout: Prevents modifications to set light levels on the
GRAFIK Eye QS control unit. Only temporary changes can be
made.
Scene Lockout: Prevents changing of the selected scene
or preset levels on all GRAFIK Eye QS control unit(s) and
wallstations.
Panic Mode: Activates scene 16 on assigned GRAFIK Eye QS
control unit(s) and places them in Scene Lockout. Toggle of
this closure will return controls to their status before Panic was
activated.
Timeclock Disable: Causes assigned GRAFIK Eye QS control
units to disable their internal timeclocks.
4. Partition Control: Allows independent (partition closed) or
parallel (partition open) operation of multiple GRAFIK Eye QS
control units.
5. Occupant Sensor Control
Occupant Sensor Scene 1/Off: Maintained contact so
occupant sensor can turn ON assigned GRAFIK Eye QS control
unit(s) while still allowing scene changes once room is entered.
Occupant Sensor Off Only: "Manual on, auto off." Occupant
must turn lights on manually, while still allowing energy-saving
benefits of automatic off.
6. QS Shade Control
Shade Input: Provides for remote control of GRAFIK Eye QS
shades.
Shade Preset: Allows opening and closing of shades, as well as
three programmable preset positions. Option also exists to allow
shades to stop if moving when contact closure is triggered.
Shade Raise/Lower/Stop: Allows opening and closing of
shades, as well as raise, lower, and stop functions.
7. Shade Output: Allows control of one or two groups of
AC motorized shades or projection screens through contact
closure outputs, triggered by button presses on a GRAFIK Eye
QS keypad or a GRAFIK Eye QS shade column.
Group 1 allows open/stop/close control.
Group 2 allows open/close control.
System Maximums
• QSE-IO counts as 2 zones toward system maximum of 100
zones per link
• QSE-IO counts as 1 device toward system maximum of 100
devices per link
• QSE-IO counts as 2 devices toward maximum of 3 powered by
a GRAFIK Eye QS control unit.
• 2000 ft (610 m) maximum wiring length.
200 mA