Installation procedure
a): Normal mounting
6
b): Flush mounting
1. Decide how the ON-OFF controller will be mounted: in the normal manner or
flush with the wall.
a) To mount the ON-OFF controller in the normal manner, remove the
mounting plate. Then reattach the four screws to the electrical
component box.
b) To mount the ON-OFF controller flush with the wall, make an opening in
the wall measuring 128 mm × 128 mm. The opening must be at least
85 mm deep as measured from the outside surface of the wall.
2. Remove the rear plate and connect the electrical wiring.
1) Remove the four screws located on both sides of the rear plate.
2) Either the hole in the top of the electrical component box or the hole in
the rear plate may be used to feed the electrical wiring.
3) If the hole on top is used, the rear plate should be turned upside down.
3. Secure the ON-OFF controller in place.
a) If the ON-OFF controller is being mounted in the normal manner, first
attach the rear plate to the wall using the screws and Rawl plugs
provided. Next, place the body of the ON-OFF controller over the rear
plate and secure it in place using four screws.
b) If the ON-OFF controller is being mounted flush with the wall, fit it
through the mounting plate on the wall and secure it in place using the
screws and Rawl plugs provided.
To mount the ON-OFF controller on a wall made of cinder block,
NOTE
brick, concrete, or a similar material, drill 4.8 mm diameter holes
in the wall and insert Rawl plugs to anchor the mounting screws.
Mounting plate
Electrical
component box
Hole for
electrical wiring
Rear plate
Fig. 2
OI-744-06EG