6. How to perform zone registration

To operate the ON-OFF controller properly, zone registration is required after
finishing the test run (and after setting all indoor unit addresses) using one of
the following methods.
(a) Zone registration using the remote controller (RBC-AMT31E)
Refer to page 16
(b) Zone registration using the ON-OFF controller (TCB-SC642TLE)
Refer to page 17
(c) Automatic zone registration using the ON-OFF controller (TCB-
SC642TLE)
Refer to page 18
For methods (a) and (b), you should make a zone registration table manually
before performing the registration as shown on the page 15.
For method (c), zone registration is executed automatically, proceeding from
small indoor unit address and small central addresses to larger numbers in
numerical order. For example:
Central control
address
ZONE-group
Indoor unit address
NOTE
1. An indoor unit address is assigned to each indoor unit during automatic
address operation. Each indoor unit address combines an R.C. address
and indoor unit number as follows:
This address is displayed on remote controller for UNIT No. when the UNIT
button is pressed.
2. The central address represents the zone and group number. These
addressed are assigned in ascending numerical order.
3. For details on how to set the addresses when the "1:1 model" connection
interface (TCB-PCNT30TLE) is connected for central control, refer to these
instructions and to the installation instructions of the "1:1 model"
connection interface.
1
2
3
1-1
1-2
1-3
1-4
1-1
1-2
2-1
2-2
1
1
: Indoor unit address (UNIT No.)
Indoor unit No.
Line address (Refrigerant circuit No.: R.C.
address)
4
5
6
1-5
1-6
2-3
3-1
OI-744-14EG