5.2 DIP switch setting

Name
Function
SW1
Not available
SW2
Reset
SW3
Not available
(TELE)
SW4
Configuration
SW5
Configuration
SW6
Configuration
SW7
Options 2
SW8
Options 1
(Application type)
SW9
Not available
SW10
HARC MODBUS
address
SW11
H-LINK DSW
D4, D11
H-LINK
D7
Power
D9/D10
Not used
D12
MODBUS
D13
Operation
Factory setting
Description
All in off (no function)
Reset button. To be used in case of program has been locked
Factory purposes. Never change it
Setting functions
Setting functions
Setting functions
SW7-1: 0FF-SLAVE / ON-MASTER. To be used in case of several
HARC-MODBUS in the same H-LINK address
SW7-2: OFF - EVENT CONTROL / ON - CHANGE CONTROL
SW7-3: OFF - Parity disabled / ON - Parity enabled
SW7-4: OFF - Even parity / ON - Odd parity
SW7-5: OFF - 19200 Bps / ON - 9600 Bps
SW7-(6~8): Not used
SW8-1: 0FF-PACKAGED / ON-CHILLER. To be set according units
application
SW8-2~8: Not used
All in off (no function)
HARC MODBUS address from 1 to 32 by pins 1 to 5
2-Pins DSW
SW11-1: H-LINK end resistance
SW11-2: H-LINK fuse protection
H-LINK transmission
Power supply ON/OFF
-
-
-
Modbus communication in RS485
-
Normal software operation
PMML0175A-rev.1 - 6/2008