MODEL F10 BURNER SETUP CHART with 6" diameter pipe
Actual
Nozzle
firing rate
size
GPH
1.45
1.25 x 60°/80°
1.80
1.50 x 60°/80°
2.10
1.75 x 60°/80°
2.40
2.00 x 60°/80°
2.75
2.25 x 60°/80°
2.89
2.50 x 60°/80°
MODEL F15 BURNER SETUP CHART with 6" diameter pipe
Actual
Nozzle
firing rate
size
GPH
2.55
2.00 x 45°/60°
2.85
2.25 x 45°/60°
3.10
2.50 x 45°/60°
3.65
3.00 x 45°/60°
4.30
3.50 x 45°/60°
5.14
4.00 x 45°/60°
5.60
4.50 x 45°/60°
MODEL F20 BURNER SETUP CHART with 6" diameter pipe
Actual
firing
Nozzle
pressure
rate
size
GPH
3.50
2.50 x 45°/60°
4.00
3.00 x 45°/60°
4.65
3.50 x 45°/60°
5.30
4.00 x 45°/60°
6.00
4.50 x 45°/60°
3436
Pump
pressure
PSI
145
145
145
145
150
145
Pump
pressure
PSI
160
160
150
150
150
165
155
20 Ft.
pipe length
Pump
Head
setting
Air setting
PSI
Low fire Main flame Low fire Main flame Low fire Main flame Low fire Main flame
195
0.5
2.1
177
2.0
2.2
176
3.5
2.7
160
4.5
3.0
177
5.0
3.0
20 Ft.
Head
pipe length
setting
Air Setting
1.5
2.3
2.0
2.8
2.5
3.5
3.5
4.2
4.5
5.2
5.0
6.0
20 Ft.
Head
pipe length
setting
Air Setting
0.0
2.0
1.0
2.3
2.0
2.3
3.0
2.9
4.0
3.5
4.5
5.5
5.0
6.1
50 Ft.
pipe length
Air setting
2.8
2.1
2.8
3.0
2.2
3.0
3.4
2.7
3.5
3.8
3.0
4.0
5.3
3.3
5.4
4
50 Ft.
80 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.4
2.4
2.8
2.9
3.5
3.6
4.2
4.3
5.2
5.5
6.0
7.0
50 Ft.
80 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.0
2.1
2.3
2.4
2.3
2.4
3.0
3.0
4.1
4.1
5.6
5.6
6.2
6.3
80 Ft.
pipe length
Air setting
2.1
2.9
2.3
3.1
2.9
3.8
3.0
4.1
3.3
5.4
100 Ft.
pipe length
Air Setting
2.5
2.9
3.7
4.4
6.5
8.0
100 Ft.
pipe length
Air Setting
2.2
2.4
2.4
3.1
4.2
5.7
6.4
100 Ft.
pipe length
Air setting
2.1
2.9
2.3
3.1
3.1
4.5
3.1
4.5
3.5
5.7