Johnson Controls M9320-HGA-4 Guia De Instalacion página 9

M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4
Technical Specifications
Product Code
Control Type
Power Requirements
Transformer Sizing Requirements
Input Signal/Adjustments
Control Impedance
Feedback Signal
Running Torque
Rotation Time
Rotation Time Autocalibration
Product Code
Control Type
Power Requirements
Transformer Sizing Requirements
Input Signal/Adjustments
Control Impedance
Feedback Signal
Running Torque
Rotation Time
Rotation Time Autocalibration
Product warranty
This product is covered by a limited warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty.
Patents
Patents:
http://jcipat.com
M9320-HGA-4
On/Off Floating
Proportional
24 VAC ± 20%, 5.7 VA running
24 VDC ± 10%, 2.1 W running
≥ 7 VA
24 VAC ±20%,
DC 0 (2) to 10 V or 0
(4) to 20 mA with field
24 VDC ± 10%
furnished 500 ohm 1/4 W
resistor
Offset: DC 0 to 10 V
Span: DC 2 to 10 V
4.7k ohm
100k ohm
DC 0 (2) to 10 V
in)
20 Nm (180 lb
90 s
35 s
M9335-HGA-4
On/Off Floating
Proportional
24 VAC ± 20%, 6.1 VA running
24 VDC ± 10%, 2.1 W running
≥ 7 VA
24 VAC ±20%,
DC 0 (2) to 10 V or 0
(4) to 20 mA with field
24 VDC ± 10%
furnished 500 ohm 1/4 W
resistor
Offset: DC 0 TO 10 V
Span: DC 2 to 10 V
4.7k ohm
100k ohm
DC 0 (2) to 10 V
in)
35 Nm (310 lb
150 s
75 s
9
M9320-AUA-4
On/Off Floating
Norminal AC 230 V at 50Hz: 0.04
AC 100 to 240V (AC 85 to 265 V) at
50/60 Hz
M9335-AUA-4
On/Off Floating
Norminal AC 230 V at 50Hz: 0.04
AC 100 to 240 V (AC 85 to 265 V) at
50/60 Hz
14-01480-00014 Rev.A