Technical Specifications

Mains voltage/
consumption
»MASTER-Relay«
(13,14)
»ADD-Relay«
(23, 24)
»START-INPUT«
(St+, STI)
»ANALOG-OUTPUT«
(AN+, GND)
Data buffer in case
of power failure
230 VAC (+/-10 %), 50–60Hz --- 2.6VA
Contact (NO), max. 4 A/230 V
n Contact will close as soon as the current
intensity > 0%.
Important: Connect a load relay with a higher
switching power between SLS-1
Contact (NO), max. 4 A/230 V
n Contact will close as soon as the programmed
threshold value is reached.
n Contact will remain open as long as threshold
value is not reached.
Important: Connect an additional load relay when
exceeding current specified between SLS-1
(lighting) load!
Connection terminal for an external timer (optional).
Important: Ensure to use a potential-free contact (NO)
since an internal 12V (7 mA) is used on these terminals.
Connection for DIM ballast (1–10V) or light dimmer
with 0–10V control input
I sink = max. 800 mA (ballast 1–10V)
I drive = max. 80 mA (0–10V output)
Note: approx. 200 dimmable ballast lights
(1–10V current sink) can be connected directly to
a single SLS-1
.
+
n Internal software timer = maximum 3 hours
n All other parameters are permanently stored in
non-volatile RAM of the processor.
10
and lighting load!
+