Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Fan control is a normally open SPST switch which
closes on a rise in temperature and has an adjustable
temperature setting.
The Limit control is a normally closed SPST switch which
opens on a rise in temperature to limit the maximum
allowable temperature and has an adjustable tempera-
ture setting.
THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.
WARNING
!
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt,
low or line voltage, have it inspected by a quali-
fied heating and air conditioning contractor or a
licensed electrician.
AC ELECTRICAL RATINGS:
8 Amps at 120 VAC or 4 Amps at 240 VAC
Pilot Duty: 125 VA
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
All manuals and user guides at all-guides.com
Printed in U.S.A.
757-1 Fan Control
758-1 Limit Control
INSTALLATION INSTRUCTIONS
This control is particularly well suited for use where space
limitations are a problem. The small bimetal sensing
element is completely in the air stream to give quick
response. This control has a snap-action switch with
heavy duty contacts.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation.
Following installation or replacement, follow
appliance manufacturers' recommended instal-
lation/service instructions to insure proper op-
eration.
Temperature Ratings:
Fan control - Variable 70° to 160°F (21° to 71°C).
Fixed differential 25°F (14°C)
Limit control - Variable 110° to 200°F (43° to 93°C).
Fixed differential 25°F (14°C)
DESCRIPTION
PRECAUTIONS
SPECIFICATIONS
PART NO. 37-5788A
9721
loading

Resumen de contenidos para Emerson White-Rodgers 757-1

  • Página 1 Fixed differential 25°F (14°C) Pilot Duty: 125 VA Limit control - Variable 110° to 200°F (43° to 93°C). Fixed differential 25°F (14°C) WHITE-RODGERS DIVISION PART NO. 37-5788A EMERSON ELECTRIC CO. Printed in U.S.A. 9797 REAVIS ROAD 9721 ST. LOUIS, MISSOURI 63123-5398...
  • Página 2 All manuals and user guides at all-guides.com INSTALLATION This control is designed for flush mounting and to be Follow the original equipment manufacturers' recommen- located directly in the air stream dations for proper location. Wiring All wiring must conform to local and national electrical codes and ordinances. Follow the original equipment manufacturer's recommendations for proper wiring.
  • Página 3 14°C (25°F) Commutateur de seuil - variable de 43° à 93°C (110° à 200°F) différentiel fixe, 14°C (25°F) WHITE-RODGERS DIVISION No. DE PIÈCE 37-5788A EMERSON ELECTRIC CO. Imprimé aux États-Unis 9797 REAVIS ROAD 9721 ST. LOUIS, MISSOURI 63123-5398...
  • Página 4 All manuals and user guides at all-guides.com INSTALLATION Cette commande est conçue pour être encastrée et Suivez les recommandations du fabricant pour déterminer placée directement dans le passage d’air. l’implantation correcte. Branchements Tous les branchements doivent être conformes aux codes et règlements électriques locaux et nationaux. Suivez les recommandations de câblage du fabricant.
  • Página 5: Especificaciones

    Servicio piloto: 125 VA Diferencial fijo 14°C (25°F) Control de límite - Variable 43° a 93°C (110° a 200°F) Diferencial fijo 14°C (25°F) WHITE-RODGERS DIVISION No. DE PARTE 37-5788A EMERSON ELECTRIC CO. Impreso en EE.UU. 9797 REAVIS ROAD 9721 ST. LOUIS, MISSOURI 63123-5398...
  • Página 6: Instalacion

    All manuals and user guides at all-guides.com INSTALACION Este control ha sido diseñado para un montaje al ras y Siga las recomendaciones del fabricante del equipo origi- para ubicarse directamente en la corriente de aire. nal para encontrar la ubicación correcta. Cableado Todo el cableado tiene que cumplir con las regulaciones y los códigos eléctricos nacionales y locales.