Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Fan control is a normally open SPST switch which
closes on a rise in temperature and has an adjustable
temperature setting.
The Limit control is a normally closed SPST switch which
opens on a rise in temperature to limit the maximum
allowable temperature and has an adjustable tempera-
ture setting.
THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.
WARNING
!
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt,
low or line voltage, have it inspected by a quali-
fied heating and air conditioning contractor or a
licensed electrician.
AC ELECTRICAL RATINGS:
8 Amps at 120 VAC or 4 Amps at 240 VAC
Pilot Duty: 125 VA
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
All manuals and user guides at all-guides.com
Printed in U.S.A.
757-1 Fan Control
758-1 Limit Control
INSTALLATION INSTRUCTIONS
This control is particularly well suited for use where space
limitations are a problem. The small bimetal sensing
element is completely in the air stream to give quick
response. This control has a snap-action switch with
heavy duty contacts.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation.
Following installation or replacement, follow
appliance manufacturers' recommended instal-
lation/service instructions to insure proper op-
eration.
Temperature Ratings:
Fan control - Variable 70° to 160°F (21° to 71°C).
Fixed differential 25°F (14°C)
Limit control - Variable 110° to 200°F (43° to 93°C).
Fixed differential 25°F (14°C)
DESCRIPTION
PRECAUTIONS
SPECIFICATIONS
PART NO. 37-5788A
9721
loading

Resumen de contenidos para Emerson White-Rodgers 757-1

  • Página 5: Especificaciones

    Servicio piloto: 125 VA Diferencial fijo 14°C (25°F) Control de límite - Variable 43° a 93°C (110° a 200°F) Diferencial fijo 14°C (25°F) WHITE-RODGERS DIVISION No. DE PARTE 37-5788A EMERSON ELECTRIC CO. Impreso en EE.UU. 9797 REAVIS ROAD 9721 ST. LOUIS, MISSOURI 63123-5398...
  • Página 6: Instalacion

    All manuals and user guides at all-guides.com INSTALACION Este control ha sido diseñado para un montaje al ras y Siga las recomendaciones del fabricante del equipo origi- para ubicarse directamente en la corriente de aire. nal para encontrar la ubicación correcta. Cableado Todo el cableado tiene que cumplir con las regulaciones y los códigos eléctricos nacionales y locales.

Este manual también es adecuado para:

White-rodgers 758-1