continued from the previous page
Number of Pages
Parameter
20. Min.Pres.Al.H2O
21.Flow.Unit.Meas.
22. Flow sensor f.s.
23. TA calib.factor
24. TV calib.factor
26. Pumps Mnt.Interv.
27. Op. Hours P1
28. Op. Hours P2
29. Op. Hours P3
30. Op. Hours P4
Description
Pressure set point to be set based on the pressure in
the delivery circuit.
The system is stopped if the pressure falls below
the set point for more than 1 minute: the display
shows AL H2O.
Attempted automatic reset 3 times after one minute
and total block with manual reset at the fourth
intervention. At this point the control unit indicates
AL 64: water lack.
Choice of the unit of measure of the flow meter:
L/sec. – L/min. – M³h.
Choice of the full-scale value of the flow meter.
Coefficient for calibrating the amperometric
transformer
Coefficient
for
calibrating
transformer
Setting of the pump maintenance hours.
Mnt.Interv. P1, Mnt.Interv. P2, Mnt.Interv.P3,
Mnt.Interv. P4
Hours worked by pump P1
Hours worked by pump P2
Hours worked by pump P3
Hours worked by pump P4
ENGLISH
the
voltmetric
49
Field
Unit of
measure
0,00-:-25,5
bar
L/sec.
L/sec.
L/min.
L/min.
M³h.
M³h.
0-:-99999
hours
0-:-99999
hours
0-:-99999
hours
0-:-99999
hours
0-:-99999
hours
DAB
Extended
SetUp
0,5
M³h.
00
00
00
4500