INSTALLATION

3.
WARNING: the installation of the device must be exclusi-
vely done by qualified personnel, following the regulations
in force and the guidelines for KNX/EIB installations.
3.1

WARNINGS FOR KNX/EIB INSTALLATIONS

1. The length of the bus line between the IR movement detector and the
power supply unit must not exceed 350 metres.
2. The length of the bus line between the IR movement detector and the
most distant KNX/EIB device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable
signals and overloads.
4. Keep a distance of at least 4 mm between the individually insulated
cables of the bus line and those of the electric line (figure C).
5. Do not damage the electrical continuity conductor of the shielding
(figure D).
WARNING: the unused bus signal cables and the electrical
continuity conductor must never touch elements under
power or the earth conductor!e di terra!
3.2

CORRECT INSTALLATION POSITION

In order to function correctly, the detector must be installed at a distance
from sources of heat, such as radiators, and must not be positioned in
direct sunlight.
3.3

ELECTRICAL CONNECTIONS

Figure B shows the electrical connections diagram.
1. Connect the bus cable's red wire to the terminal's red connector (+)
and the black wire to the black connector (-). Up to 4 bus lines can be
connected to the bus terminal (wires of the same colour in the same
terminal) (figure E).