1/2"
3/16"
FRAME STOP
FRAME STOP
UL Tested and Classified for Fire and Smoke Doors.
* Seals against smoke, fire, air and weather.
* Excellent compression; door latches easily.
1. The surface temperature of the frame must be above 50°F for the adhesive to bond properly.
2. Clean frame with clean wipe provided to remove dust, oil, grease and dirt. Wax coated or high gloss painted
surfaces may require roughening of the surface with a scotch brite pad or sandpaper so adhesive will prop-
erly bond.
3. Measure and pre-cut pieces to fit where seal is to mount. 1/8" clearance required between door and frame.
4. Remove protective backing 1 to 2 feet at a time.
5. Position on frame where illustrated.
6. Adhere by pressing firmly (approx. 15 lbs. pressure requried) straight down along entire length of gasketing.
Do not remove and relocate.
7. Make sure the seal does not impede proper closing and latching of the door.
POSITIVE PRESSURE TESTED GASKETING MATERIALS
FOR FIRE DOORS
FOR APPLICATION TO HOLLOW-METAL-TYPE FIRE DOORS
RATED UP TO 3 HOURS AND WOOD-TYPE FIRE DOORS
RATED UP TO 1-1/2 HOURS.
Smoke & Draft Control Gasketing (Category H) tested to UL 1784; meets
requirements of NFPA 105, IBC for use on 'S' label doors.
Sealing System (Category G) for use on category B
NGP-EDGE
ESS
®
wood type fire doors rated up to 90 minutes, single swing up to 4'0" x
9'0" and pairs up to 8'0" x 9'0".
2.15
National Guard Products Inc.
Self Adhesive
Fire & Smoke Seal
HEAD&
LATCH JAMB
DOOR
DOOR
HINGE JAMB
INSTALLATION INSTRUCTIONS
CATEGORY G, H
9850
STORAGE AND SHELF LIFE
The adhesive on this seal has a shelf life of
one year stored at 75°F and 50% relative
1-800-647-7874
Made in USA
S
10C
humidity or less
loading

Resumen de contenidos para NGP 9850

  • Página 1 National Guard Products Inc. 1-800-647-7874 9850 Self Adhesive Fire & Smoke Seal 1/2" HEAD& 3/16" LATCH JAMB Made in USA FRAME STOP DOOR DOOR FRAME STOP HINGE JAMB UL Tested and Classified for Fire and Smoke Doors. * Seals against smoke, fire, air and weather.
  • Página 2 UL 1784; cumple con los requisitos de NFPA 105, IBC para usarse en puertas etiquetadas “S”. de 75ºF y una humedad relativa de 50% o menos Sistema de Sellado NGP-EDGE (Categoría G) para usarse en puertas ® cortafuego de madera categoría B certificadas hasta 90 minutos, para puertas sencillas abatibles de hasta 4'0"...