Water softener ELETTRONIC with AUTOTROL digital head logix
Phase 4b: Set the safety regeneration mode
(only for programmers 760 with volumetric control)
IMPORTANT
Legislative Decree 443/90 establishes the obligation for automatic regeneration at least once
every 4 days.
• If you use 740, move to phase 5.
• Set the number of days for safety regeneration frequency
also without completing the cycle.
• Days "0" is the default value.
• The days can be set starting from ½ day (0.5) to 99 days.
• To change, press SET in order to have the value "0" flash.
• Use buttons UP and DOWN to change the number of days.
• Press SET to confirm the regeneration frequency and move
to the next cycle.
Phase 5: Set quantity of salt
IMPORTANT
Never change this value.
Should this accidentally happen, refer to the related column on the table.
• Set the desired regenerating quantity of salt.
• The default value is "S" , medium level.
• 3 levels of salt are available:
L – low level;
S – medium level;
H – high level;
• Choose the level that is more appropriate for the softener model.
• To change salt setting, press SET and use UP and DOWN to select the desired setting.
• Press SET to confirm the setting and move to the next parameter.
Set low salt quantity
22
(regenerating agent quantity)
Set salt standard quality
Set high salt quantity