8.1
Technical specifications
Output power
Electrical supply network
◗ Rated input voltage
◗ Input voltage range
◗ Frequency
◗ Power factor
◗ Leakage current
Load output
◗ Voltage
◗ Frequency
◗ Harmonic distortion
◗ Overload capacity
Battery
Environment
◗ Operating temperature range
◗ Relative humidity
◗ Storage temperature range
◗ Altitude
Noise level
(1) If the output voltage is 200V — 250V, the output power is 5000VA / 4500W.
(2) With one EXB module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the Personal Solution-Pac software.
(5) Frequency-converter mode is programmable using the Personal Solution-Pac software.
(6) Step-down transformer is available for 120V output.
MX 5000
5000 VA
4500 W
Single phase 208 V
120/156 V to 280 V
50/60 Hz (autoselect)
> 0.99
7 mA
Single phase 208 V ±3%
50/60 Hz ±0.5%
< 3%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
15 x 12V - 5 Ah, sealed lead acid, maintenance free
20% to 90% (non-condensing)
< 45 dBA
/
(1)
(2)
(3)
(4)
(5)
0°C to 40°C
-25°C to 40°C
1000 m
8. Appendices
MX EXB
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
86-87021-00 A01 - Page 39