3.5 CE marking
The CE marking shows that the products
comply with the basic requirements of the
applicable directives as stated on the de-
claration of conformity.
The declaration of conformity can be
viewed at the manufacturer's site.
4 Set-up
4.1 Checking the scope of delivery
▶
Check that the scope of delivery is com-
plete.
Quant-
Component
ity
1
RED‑5
1
Installation accessories (bolts
and rawl plugs)
1
Documentation
4.2 Selecting the lines
▶
Use standard commercial lines for the
wiring.
▶
Do not use flexible lines for mains
voltage supply lines.
▶
Use insulation cables for mains voltage
supply lines (e.g. NYM 3 x 1.5).
Line cross-section
Supply line for
mains voltage
(pump or mixer
mains cable)
eBUS line (extra-
low voltage)
Sensor line (extra
low voltage)
Line length
Sensor lines
Bus lines
0020257175_03 Installation instructions
≥ 1.5 mm²
≥ 0.75 mm²
≥ 0.75 mm²
≤ 50 m
≤ 125 m
4.3 Removing the front casing
A
▶
Remove the front casing in accordance
with the illustration.
4.4 Installing the wall base
B
B
▶
Install the wall base using the appro-
priate fastening material in accordance
with the illustration.
Set-up 4
C
B
A
33