Pre-blinking time
Before any gate movement, blinker will be activated for t.PrE time, to warn
about the incoming motion.
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the opening phase.
PAUSThe gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate go on with the opening phase (command is ignored)
Select option PAUS, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the closing phase.
StoP
The gate stops and its cycle is considered as finished
APEr
The gate opens again
Select option StoP, to set up the "step-by-step" operation logic.
Select option APEr, to set up the 'always open' operation logic.
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a Start
command when the gate is open during its pause phase.
ChiU
the gate starts closing
no
command is ignored
Select option ChiU, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Apart from selected option, the start command lets the gate close if it has
been stopped by a stop command or if the automatic closing was not
enabled.