Machine Card And Logbook - Toshiba MMY-MUP0801HT8P-E Manual De Instrucciones

Ocultar thumbs Ver también para MMY-MUP0801HT8P-E:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
1 : Compressor 1 side
2 : Compressor 2 side
00: Compressor 1 side or Compressor 2 side
P07
04: Heat sink
P10
Detected indoor unit address
P11
P13
01: TS condition
P15
02: TD condition
P17
P19
Detected outdoor unit number
P20
1 : Fan P.C. board 1
P22
2 : Fan P.C. board 2
1 : Compressor 1 side
P26
2 : Compressor 2 side
11: Compressor 1 side
P29
21: Compressor 2 side
*1 Inverter quantity information
01: Compressor 1 trouble
02: Compressor 2 trouble
03: Compressor 1 and 2 trouble
08: Fan 1 trouble
09: Compressor 1, Fan 1 trouble
0A: Compressor 2, Fan 1 trouble
0B: Compressor 1 and 2, Fan 1 trouble
10: Fan 2 trouble
173-EN
IM_1141001201-2_Book.indd 87
IM_1141001201-2_Book.indd 87
Check code name
Heat sink overheating trouble
Heat sink condensation trouble
Indoor overflow error
Outdoor heat exchanger freezing trouble
Outdoor unit flow back error detected
Gas leak detection
Discharge temperature TD2 trouble
4-way valve inverse trouble
High-pressure protective operation
Outdoor fan inverter trouble
IPM short protection trouble
Compressor position detecting circuit system trouble
A value from 0 to F is displayed in " ".
11: Compressor 1, Fan 2 trouble
12: Compressor 2, Fan 2 trouble
13: Compressor 1 and 2, Fan 2 trouble
18: Fan 1 and 2 trouble
19: Compressor 1, Fan 1 and 2 trouble
1A: Compressor 2, Fan 1 and 2 trouble
1B: Compressor 1 and 2, Fan 1 and 2 trouble
– 87 –
14

Machine card and logbook

Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely
before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party
concerned or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the
quantities of refrigerant which have been transferred from the system on each occasion;
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.
174-EN
5/2/2564 BE 16:27
5/2/2564 BE 16:27

Hide quick links:

Tabla de contenido
loading

Tabla de contenido