5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a outdoor unit connection piping kit (RBM-BT14E / RBM-BT24E/ RBM-BT34E : separately
purchased) to connect each outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
the header unit.)
Liquid piping
Figure 1
Correct
Header unit
Follower unit
Follower unit
A
B
C
Main pipe
To the indoor unit
Gas piping
Figure 3
Correct
Header unit
Follower unit
Follower unit
A
B
C
Main pipe
To the indoor unit
Extension valve
• When attaching a Y-shaped branching joint for the gas side, attach it level with the ground (Be sure not to
exceed ±15 degrees.). Regarding a T-shape branching joint for the liquid side, there is no restriction for its angle.
(Horizontal line)
Within ±15 degrees
A
(A arrow view)
B
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep
the straight part of at least 500 mm at the inlet.
119-EN
IM_1141001201-2_Book.indd 60
IM_1141001201-2_Book.indd 60
Figure 2
Incorrect
Header unit
Follower unit
Follower unit
A
B
C
Incorrect
Main pipe
To the indoor unit
[Inverse connection of a gas-side branch unit]
Figure 4
Incorrect
Header unit
Follower unit
Follower unit
A
B
C
Main pipe
To the indoor unit
To gas-side branch unit
(Horizontal line)
Do not connect
Within ±15
the branching
degrees
vertically.
(B arrow view)
At a level position
When drawing pipes downward
Figure 5
Correct
Header unit
Follower unit
Follower unit
A
B
C
L-shaped
pipe
To gas-side branch
To gas-side branch
unit
unit
• Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header
unit. Use an extension valve for installation (See the figure above.).
Specify the pipe diameter in advance to allow for adding another unit.
– 60 –
[Vertical connection of branch units]
Figure 6
Incorrect
To gas-side
To gas-side
branch unit
branch unit
5/2/2564 BE 16:27
5/2/2564 BE 16:27
EN
120-EN