6. Trial running

6-1 Inspection and confirmation before debugging
1) Check and make sure the refrigerating pipeline and communication
line between the indoor and outdoor units are in the same refrigerating
system, or some operation fault may occur.
2) The voltage power supply is within ±10% of the rated voltage.
3) Check and make sure the power supply line and control line are
correctly connected.
4) Make sure there is not short circuit before the system is electrified.
5) Make sure all units have passed the 24h nitrogen pressure
maintaining test (4.0MPa).
6) Make sure the system is fully vacuumized, dried and filled with the
refrigerant as per the specification.
6-2 Preparation before debugging
1) Calculate the amount of refrigerant to be refilled as per the field liquid
tube length.
2) Prepare the required refrigerant.
3) Prepare the system planar drawing, system pipeline drawing and
control line drawing.
4) Record the well set address codes on the system planar drawing.
5) Turn on the outdoor unit power supply switch in advance, and make
sure it is connected for more than 12h to make the heater heating the
compressor oil.
6) Fully open the outdoor unit gas tube check valve, liquid tube check
valve and oil balance valve, or the machine may be damaged.
7) Check if the phase sequence of the outdoor unit power supply is
correct.
8) Check if all dialing switches of the outdoor and indoor units are set as
per the product technical requirement.
6-3 Name filling of connected systems
When setting several indoor units, each connecting system of the indoor
unit and outdoor units shall be identified and named and recorded on the
nameplate of outdoor unit electrical control box cover.
Indoor unit type
Room name
E.g.: 1st system room(A) on floor 2
recorded as: -2F-1A
Fig.6.1 Name filling of connected systems
6-4 Precautions against refrigerant leakage
1) The refrigerant itself of this air conditioner is harmless, nonflammable
and safe.
2) The air conditioner room shall be of a suitable space size so that the
refrigerant concentration will not go beyond the limit even if leakage
happens, and some necessary measures can be taken additionally.
3) The critical gas concentration harmless for the human body is
³
0.3kg/m .
4) Confirm the critical concentration as per the following steps and take
necessary measures correspondingly.
1. Calculate the full volume of refrigerant to be filled (A[kg])
Full refrigerant volume = refrigerant volume at delivery (see the
nameplate) + refrigerant volume to be refilled for the corresponding tube
length
2. Calculate the indoor cubage (B[m ]) (as per the minimum cubage)
3. Calculate the refrigerant concentration
A[kg]
≤ critical concentration:
B[m³]
³
0
.
3
[
kg
/m³].
Outdoor unit
Indoor unit
Fig.6.2 Refrigerant leakage
5) Measures against exceeding the critical concentration
1. To control the refrigerant concentration below the critical
concentration, a mechanical air ventilating device shall be installed (for
frequent air ventilating).
2.If frequent air ventilating cannot be realized, please install a leakage
warning and detecting apparatus interlinked with the mechanical air
ventilating device.
3.The leakage warning and detecting apparatus shall be installed in a
place with dense refrigerant accumulation.
b. Mechanical air ventilating device
Air inlet
Fig.6.3 Air exchange
6-5 Hand over to the client
1) The Instruction Manual for the indoor unit, Instruction Manual for the
outdoor unit and Direction for Customer Service must be submitted to the
client.
2) Explain the content of Instruction Manual to the client carefully.
6-6 Correct Disposal of this product
The european directive 2012/19 /UE on wasted
electrical
requires that household electrical appliances must
not be disposed of in the normal unsorted municipal
waste
separately in order to optimize the recovery and
recycling of the materials they contain, and reduce
DISPOSAL: Do not
the impact on human health and the environment.
dispose this
The crossed out "wheeled bin" symbol on the product
product as
reminds you of your obligation, that when you
unsorted municipal
disposed of the appliances, it must be separately
waste. Collection
of such waste
collected. Consumers should contact their local
separately for
authority or retailer for information concerning the
special treatment
correct disposal of their old appliance.
is necessary.
17
Indoor unit
Indoor unit
Indoor unit
Room of refrigerant leakage
Indoor unit
a. Air exchange
and
electronic
equipments
stream.
appliances
must
be
V.1
V.1
(WEEE),
collected