6. TEST RUNNING

Operate according to "gist for test running" on the electric control box
cover.
CAUTION
Test running can not start until the outdoor unit has been
connected to the power for 12hr.
Test running can not start until all the valves are affirmed
open.
Never make the forced running. (Or the protector sits back,
danger will occur.)

7. CONFIGURATION

7.1 Overview
This chapter describes how the system configuration can be
implemented once the installation is complete, and other relevant
information.
It contains the following information:
▪ Implement field settings
▪ Energy-saving and optimized operation
i
Information
The installation personnel should read this chapter.
7.2
Dial Switch Settings
Dial code definitions:
means 0
Table 7-1
For 200 to 280 unit only
0-F
The number of indoor units is in the range 0-15
0-9 on ENC1 indicate 0-9 indoor units;
A-F on ENC1 indicate 10-15 indoor units
ENC1
0
1 2 3
&
S9-3
0-F
The number of indoor units is in the range 16-31
0-9 on ENC1 indicate 16-25 indoor units;
A-F on ENC1 indicate 26-31 indoor units
1
1 2 3
Outdoor unit network address setting,
ENC3
0-7
Only 0 to 7 should be selected (default is 0).
0
When connected to 2nd generation DC indoor unit(default)
S1-1
1
When connected to AC or 1st generation DC indoor unit
1 2 3
0
Auto addressing (default)
S1-2
Clear indoor unit addresses
1
1 2 3
Reserved
0
S1-3
1
Factory test only
1 2 3
Auto priority (default)
000
Cooling priority
100
010
First ON priority
S2
1 2 3
110
Heating only
001
Cooling only
Other combinations,Heating priority
00
Outdoor unit capacity,280
Outdoor unit capacity,260
01
S9-1
S9-2
Reserved
10
1 2 3
Outdoor unit capacity,224/200(customer)
11
means 1
Table 7-1
Table 7-2
For 335 unit only,335 unit adopt different PCB
0-F
The number of indoor units is in the range 0-15
0-9 on ENC1 indicate 0-9 indoor units;
0
A-F on ENC1 indicate 10-15 indoor units
ENC1
1 2 3
&
S9-3
0-F
The number of indoor units is in the range 16-31
0-9 on ENC1 indicate 16-25 indoor units;
1
A-F on ENC1 indicate 26-31 indoor units
1 2 3
Outdoor unit network address setting,
0-7
ENC3
Only 0 to 7 should be selected (default is 0).
0
When connected to 2nd generation DC indoor unit(default)
S1-1
When connected to AC or 1st generation DC indoor unit
1
1 2 3
0
Auto addressing (default)
S1-2
1
Clear indoor unit addresses
1 2 3
0
Reserved
S1-3
1
Reserved
1 2 3
Auto priority (default)
000
100
Cooling priority
First ON priority
010
S2
Heating only
110
1 2 3
Cooling only
001
Other combinations,Heating priority
Reserved
0
S9-1
1
Outdoor unit capacity,12HP
1 2 3
Reserved
0
S9-2
1
Factory test only
1 2 3
Please cut off the power supply when changing the dial switch
20