Isection I: User; Versions Available; Machine Identification; Declared Conditions Of Use - emmeti EH Serie Manual De Instalacion Y Uso

Ocultar thumbs Ver también para EH Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

I
SECTION I: USER
I.1

VERSIONS AVAILABLE

The available versions belonging to this product range are listed below.
After having identified the unit, you can use the following table to find
out about some of the machine's features.
E
Water production unit
H
Heat pump
T
400 V/3 Ph/50 Hz
cooling capacity (kW) (*)
(*) The power value used to identify the model is approximate, for the
exact value, identify the machine and consult the enclosed documents
(A1 Technical Data).
I.1.1

MACHINE IDENTIFICATION

The units feature a serial number plate located on the side which
includes machine identification data.
I.2

DECLARED CONDITIONS OF USE

EH units are packaged cooling cycle reversible heat pumps with air
evaporation/condensation and axial fans complete with a hydraulic
pump.
They are suitable in air conditioning installations and industrial
processes where chilled and hot water is required, not for human
consumption.
The units are designed for outdoor installation.
DANGER!
The machine has been designed and manufactured
solely and exclusively to function as an air
evaporation heat pump; any other use is strictly
PROHIBITED. Installing the machine in an explosive
environment is prohibited.
DANGER!
The machine is designed for outdoor installation.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
IMPORTANT!
The unit will function correctly only if the
instructions for use are scrupulously followed, if
the specified clearances are complied with during
installation, as well as the use restrictions indicated
in this manual.
Year
18
19
25
19
30
19
I.2.1

FUNCTIONING LIMITS

T
(°C)
48
44
38
20
10
0
1
-10
-15
-18
t
(°C)
65
60
55
50
45
40
35
30
25
-30
-20
-10
T (°C) = Air temperature (B.S.).
t (°C) = Temperature of the water produced.
Standard functioning
Operation FI15
In summer mode:
Maximum water inlet temperature 25°C.
In winter mode:
Maximum water inlet temperature 55°C
Permitted temperature differentials through the heat exchangers
○ Temperature differential ∆T = 4 ÷ 8°C.
○ Minimun water pressure 0,5 Barg.
○ Maximum water pressure 6 Barg.
N.B.:
For evaporator outlet water at a temperature below 5°C, please contact
the EMMETI pre-sales service before ordering.
In the permitted field of operation, the compressor and inverter are
protected by a controller by means of continuous monitoring of the
current absorbed by the compressor, operating pressure and output
temperature. The compressor can modulate the rotation speed
automatically, regardless of the set-point request if it goes out of its
proper field of operation.
22
SECTION I: USER
Summer mode
5
10 11 12
17
19
Winter mode
0
10
20
30
t
(°C)
40
50
T
(°C)
Tabla de contenido
loading

Este manual también es adecuado para:

Eh1819t-dcEh2519t-dcEh3019t-dc

Tabla de contenido