Ac Wiring Instructions - Tuthill FILL-RITE H Serie Manual De Instalación Y Operación

Bombas de transferencia de combustible
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 48
|
115V AC Wiring Instructions for FR600 / SD600 AC Fuel Transfer Pumps
• All pumps will operate at the rated nameplate voltage.
• AC power should be supplied to the pump from a dedicated circuit with a 15 amp circuit protection. No other
• Wiring must be of sufficient size to carry the correct current for the pump.
• Voltage drop will vary with distance to pump and size of wire; refer to the National Electrical Code (NEC) or local codes
• Ensure proper grounding to avoid electrocution.
• Each Tuthill motor is labeled as explosion-proof for hazardous locations Class I / Division 1. It is highly recommended
• Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national
• Ground wire in supply wiring MUST be connected to the ground screw inside the junction box.
Voltage drop in wiring varies depending on the distance from the electrical source to the pump and the gauge of the wire
used. Tuthill recommends referring to national, international, or local electrical codes to ensure the wire is of the correct
size for your application. The following chart is to be used as a reference and is not a substitute to electrical codes.
Maximum Linear Distance (FT) of Solid and Stranded Copper Wire Length by Gauge
fillrite.com | tuthill.com
H-SERIES FUEL TRANSFER PUMPS
equipment should be powered by this circuit.
for voltage drop compensation to be sure you are using the correct size wire for your application. Undersized wires can
overheat and cause a fire.
that any repairs be done by an authorized distributor to avoid voiding the warranty. It is very important to maintain the
explosion-proof integrity of the motor and system components.
electrical codes (NEC/ANSI/NFPA 70, NFPA30, and NFPA 30A) as appropriate to the intended use of the pump.
The pump must be properly grounded. Improper installation or use of this pump can result in serious bodily injury or death.
AWG
16
Solid
39
Wire
Stranded
38
INSTALLATION AND OPERATION MANUAL
14
12
10
62
99
158
61
96
154
8
6
4
250
245
389
620
10

Hide quick links:

Tabla de contenido
loading

Tabla de contenido