step 2: Drill Piping Hole
1 Determine hole positions according to the
diagram. Drill one (1) hole (Ф55 or Ф70 mm)
in the wall at a slight downward slant to the
outdoor side.
Piping hole
Ф55 mm
Ф70 mm
2 The inclination must be between 5 - 10mm in
order to ensure a good drain of condensed
water generated by the indoor unit.
Indoor
Wall pipe
5-10mm
3 Insert the wall pipe into the hole to prevent
and wiring from being damaged when passing
through the whole.
4 Always use a wall hole conduit when drilling
metal grids, metal plates or the like.
5 For cooling capacity over 6000W models,
remove and dispose the two polystyrene lateral
rear supports from the indoor unit before the
installation.
10
Model
Cooling capacity <6000W
Cooling capacity >6000W
Outdoor
Seal putty
Ø55
or Ø70
Wall
Remove both supports
step 3: installation of Drain Hose
1 Connect the drain hose to the outlet pipe of the
indoor unit. bind the joint with vinyl tape.
Outlet pipe of
indoor unit
Vinyl tape
2 Put the drain hose into insulating pipe.
Outlet pipe of
indoor unit
Vinyl tape Insulating pipe
Outlet pipe of
indoor unit
Drain hose
Drain hose (narrow)