NOTE: Follow the preservative manufacturer's
instructions for the proper use of water
preservative.
INSPECT EYEWASH UNIT
1.
Visually inspect the eyewash unit weekly for
cleanliness and proper solution level (per ANSI
Standard Z358.1-2014).
2. Activate the eyewash unit each time the solution is
replaced to ensure proper operation. If the unit is not
working properly, remove it from the hazard area and
contact Uline immediately.
• Check the sprayheads' water spray pattern for an
even, continuous flow. The sprayheads are attached
to the tray with screws and can be detached from the
tray for cleaning or obstruction removal, if necessary,
and reattached. Use a 9/64" hex-head Allen wrench
to remove and reinstall the sprayheads.
• Check the water supply hose at the basin of the
eyewash unit for cracks, leaks or wear.
• Check the entire unit for possible water leakage.
• Check the solution for contamination and replace
with fresh solution, if necessary.
PAGE 4 OF 12
MAINTENANCE
CLEAN EYEWASH UNIT
When using potable water and water preservative
(recommended):
1. Carefully remove the eyewash tank from the
pedestal and drain the water solution from the tank
(dispose of the solution properly).
2. Clean the inside of the tank using warm water and a
mild soap product; rinse thoroughly.
3. Refill the eyewash tank. Follow instructions of the
preservative manufacturer for the proper use of
water preservative.
4. Reinstall the eyewash tank.
When using potable water only:
1.
Empty the tank any time from once per week to
once per month, depending on the quality of your
water supply. The manufacturer and Uline are not
responsible for variations in the water supply.
2. Clean the inside of the tank using warm water and
mild soap. Rinse the tank thoroughly with warm
water.
3. Refill the eyewash tank with tepid, potable water.
1-800-295-5510