5. Commissioning, operation
5.5 Overview of parameters
Menu
Description
item
EN
INI
Initialisation menu
UNIF
Flow unit
TIF
Min / Max flow setting, only active with UNIF = %
Zero point setting /"Autozero" version, only active
0SET
when UNIF ≠ %
mu_F
Flow multiplier, only active when UNIF ≠ %
uniT
Temperature unit
PIPD
Pipeline diameter in mm, only active when UNIF ≠ %
SP1 / SP2
Hysteresis function: Switch point (switching output 1
if applicable 2)
FH1 / FH2
Window function
Window high (switching output 1, if applicable 2)
RP1 / RP2
Hysteresis function: Reset point (switching output 1,
if applicable 2)
FL1 / FL2
Window function
Window low (switching output 1, if applicable 2)
EF
Extended programming functions
RES
Reset the parameters to factory setting
DS1 /
Switching delay time, which must occur without
DS2
interruption before any electrical signal change occurs
(SP1, if applicable SP2)
16
Parameter
-
m/s, l/min, m3/h(m³/h), FT/s, FT3m (ft³/s),
UGPm (US Gal/min), GPm (Imp. Gal/min), %
MIN (NO/YES) sets current flow value to 0 %
MAX (NO/YES) sets current flow value to 100 %
YES/NO
YES sets current flow value to zero
0.10 ... 10.00
°C, °F
10 ... 1,000
0.05 ... 3 m/s [0.17... 9.84 ft/s]
1.7 ... 100 %
If SP2 is configured for temperature:
-18.2 ... +85 °C [-0.8 ... +185 °F]
-
0 ... 2.950 m/s [0 ... 9.67 ft/s]
0 ... 98.3 %
If SP2 is configured for temperature:
-20 ... +78.2 °C [-4 ... +172.8 °F]
-
-
YES/NO
0.00 ... 65.00 s
WIKA operating instructions flow switch, model FSD-4
Factory
setting
-
m/s
-
-
1.00
°C
25
3.000 (m/s)
-
2.700 (m/s)
-
-
-
0.00 s