G e n e r a l i n f o r m a t i o n :
For application in refrigeration systems in compliance
with standard EN 378.
A professional and appropriate storage and allocation
of the devices is mandatory.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• According to EN 13313 it is intended for use by
persons having the appropriate knowledge and
skill.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Before installation or service disconnect all
voltages from system and device.
• Do not exceed the specified maximum ratings for
pressure, temperature, voltage and current.
• Keep temperatures within nominal limits. Switch
housing temperature must not exceed 70°C in
high medium temperature applications.
S e t t i n g :
• CS3 Pressure switches are factory preset to a specific
value (see label).
• Note: Cut-in/cut-out and differential may not be
readjusted by the customer (otherwise product
looses warranty).
F u n c t i o n / T y p e o f s w i t c h : ( F i g . 1 & 2 )
Fig. 1: Pressure switch with automatic reset
Fig. 2: High pressure cut-out (manual reset)
F i g . 1
F i g . 2
4
1
1
2
+
P
P
-
CS3 with automatic reset:
CS3 Pressure switches are equipped with a SPDT snap
action contact switching from 1-2 to 1-4 on rising and
from 1-4 to 1-2 on falling pressure.
CS3 with manual reset:
Reaching the preset switching point contact 1-2
opens and latches. After the pressure drops by
appr.13-25 bar depending on pressure range the
switch can be reset by pushing the reset button.
I n s t a l l a t i o n :
• Mounting direction: any
• Do not apply torsional force to housing assembly
during mounting (Fig. 3).
P r e s s u r e c o n n e c t i o n : s e e F i g . 3
= Copper gasket
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Operating instructions
Pressure Switch Series CS3
E l e c t r i c a l c o n n e c t i o n :
Note: Entire electrical connections have to comply
with local regulations. To maintain IP65, proper
installation is mandatory.
Connection with cables PS3-Nxx/-2xx/-4xx
(Fig.4 & 5):
bk = black;
− Plug meets requirements of DIN 40050/IEC 529/
EN60529.
− Plug has an integrated gasket.
− Fasten screw with max. torque 0,05Nm.
− Plug cannot be repaired, in case of failure replace
product.
− Only one mounting position is possible.
P r e s s u r e T e s t :
After completion of installation, a pressure test must be
carried out as follows:
– according to EN 378 for systems which must
comply with European pressure equipment
directive 2014/68/EU.
– to maximum working pressure of system for other
applications.
W a r n i n g :
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
T i g h t n e s s T e s t :
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages
of external joints. The allowable leakage rate must be
according system manufacturer's specification.
S e r v i c e / M a i n t e n a n c e :
4
In case of repair work or replacing the control always
use new gaskets (Fig 3 –
2
+
-
T y p e c o d e :
CS3 -
e.g. CS3 – W 8 S
Function
B = Pressure cut out, external manual reset,
type approval, EN 12263, PZH
S = Safety pressure cut out, internal manual
reset, type approval, EN 12263 PZHH
W = Pressure limiter, automatic, type approval,
EN 12263, PSH
Note: Function types B or S protect against high
pressure
Pressure
setting
range
7/P = 40...70 bar
8/Q = 60...140bar
Note:
Pressure connection
S = 7/16"-20 UNF female with schraeder opener,
(with snubber)
www.climate.emerson.com/en-gb
bl = blue;
br = brown
).
Max. allowable
Pressure
Pressure
(PS)
90 bar
140 bar
7/8 Standard contacts
P/Q Microswitch
Date: 08.10.2019
T e c h n i c a l D a t a :
Max. working
pressure PS
Test pressure PT
Electrical rating
Inductive load
(AC15)
Inductive load
0.1A 230VDC
(DC)
Motor rating amps
(FLA)
Lock rotor amps
(LRA)
Note: For electronic applications with low electrical
loads (current <100 mA) standard contacts are not
suitable.
Protection class
(EN 60529)
Vibration
resistance
Temperatures
Ambient (housing)
Note: For high temperature applications, i.e. medium
temperatures between 70°C and 150°C, the maximum
ambient temperature must be derated as per drawing.
see Fig. 6;
Tm = Medium temperature,
Ta = Ambient temperature
E.g.: On medium temperature 120°C the ambient
temperature of 55°C around the switch housing should not
be exceeded.
Temperatures
Storage/transport
-40°C...+70°C
Medium
-40°C... +150°C
Medium
CO
compatibility
Marking
acc. Low Voltage Directive
0035 acc. to PED 2014/68/EU
(File No. E85974)
Test
(PT)
100 bar
154 bar
CS3_OI_ML_R02_0718303.docx
Range 7/P: 90 bar
Range 8/Q: 140 bar
Range 7/P: 100 bar
Range 8/Q: 154 bar
Standard
Micro-switch
3A 230VAC
1.5A 230VAC
0.1A 230VDC
6A
2.5A
120/240VAC
120/240VAC
UL: 6A
UL: 1.5A
120/240VAC
120/240VAC
36A
15A
120/240VAC
120/240VAC
UL: 18A
UL: 10A
120/240VAC
120/240VAC
IP65 with PS3-Nxx
IP00 (without appliance socket)
4g (at 10...250 Hz)
-40°C...+70°C
(R744)
2