Communication parameters

Enter into the "modbus" sub-menu from menu 23 to edit the following parameters relative to the RS485#2:
Slave Address: from 1 to 254, default 1
Baud Rate: 9600/19200, default 9600
Parity: NONE
Commands
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
Parameters map
VARIABLE
ON/OFF
OPERATING SPEED
SETPOINT 1 TEMPERATURE
(SP1) - BYPASS
SETPOINT 2 TEMPERATURE
(SP2) - POSTHEATER
SUPPLY SPEED 1 (V1S)
SUPPLY SPEED 2 (V2S)
SUPPLY SPEED 3 ((V3S)
SUPPLY SPEED 4 ((V4S)
(SE ESISTENTE)
EXHAUST SPEED 1 (V1H)
EXHAUST SPEED 2 (V2H)
EXHAUST SPEED 3 (V3H)
EXHAUST SPEED 4 (V4H)
TIME PERIOD ENABLE
MINIMUM PERMITTED
SPEED (VMIN)
MAXIMUM PERMITTED
SPEED (VMAX)
RELATIVE HUMIDITY HR% 16BIT-INT
AIR QUALITY VOC
TEMPERATURE NTC 1
TEMPERATURE NTC 2 (EST) 16BIT-INT
TEMPERATURE NTC 3
TEMPERATURE NTC 4
ACTIVE BYPASS
ACTIVE NOFROST
ACTIVE POSTHEATER
ALARM PRESENCE
168
TYPE
BOOL
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
BOOL
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
BOOL
BOOL
BOOL
16BIT-INT
PERMITTED VALUES
TRUE, FALSE
1,2,3,4
16 ÷ SP2
SP1 ÷ 30
VMIN ÷ V2S
V1S ÷ V3S
V3S ÷ VMAX
VMIN ÷ V2H
V1H ÷ V3H
V2H ÷ V4H
V3H ÷ VMAX
TRUE, FALSE
0 ÷ VMAX
VMIN ÷ 100
0 ÷ 100
0 ÷ 100
-40 ÷ 60
-40 ÷ 60
-40 ÷ 60
-40 ÷ 60
TRUE,FALSE
TRUE,FALSE
TRUE,FALSE
(*)
READ/WRITE
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
R
R
R
R
R
R
R
R
R
R
R
R
ADDRESS
16399
16400
16401
16402
16403
16404
16405
16406
16407
16408
16409
16410
16411
8961
8964
8974
8975
8976
8977
8978
8979
8981
8982
8983
8984