2.3.4 Thermal output vs. flow rate behaviour
-
For domestic hot water (DHW) applications, the recommended nominal flow rate is 32 L/h/panel.
-
For applications towards a thermal discharge, the recommended nominal flow rate is 100 L/h/panel. For
example, towards a swimming pool or geothermal probes.
-
For direct pool heating applications, the recommended nominal flow rate is 200 L/h/panel.
The curves below are given as an indication.
35,0
30,0
25,0
20,0
15,0
10,0
5,0
0,0
0
Figure 2 : Delta T = f (Q) curves for DUALSUN Spring XXXM – 60 – 3BBPI – insulated version
30,0
25,0
20,0
15,0
10,0
5,0
0,0
0
Figure 3 : Delta T = f (Q) curves for DUALSUN Spring XXXM – 60 – 3BBPN – non-insulated version
Installation, operation and maintenance instructions - DualSun XXXM – 60 – 3BBP
Delta T° vs. flow rate and irradiation
Tamb = 25°C and Tin = 25°C - wind = 1 m/s
DualSun XXXM - 60 - 3BPPI
25
50
75
DT (G=1000 W/m2)
Delta T° vs. flow rate and irradiation
Tamb = 25°C and Tin = 25°C - wind = 1 m/s
DualSun XXXM - 60 - 3BPPN
25
50
75
DT (G=1000 W/m2)
100
125
150
FLOW RATE [L/H/PANEL
DT (G=800 W/m2)
100
125
150
FLOW RATE [L/H/PANEL
DT (G=800 W/m2)
V1.2 – March 2020
175
200
225
DT (G=500 W/m2)
175
200
225
DT (G=500 W/m2)
250
250
Page 8 sur 41