2.3.4 Thermal output vs. flow rate behaviour

-
For domestic hot water (DHW) applications, the recommended nominal flow rate is 32 L/h/panel.
-
For applications towards a thermal discharge, the recommended nominal flow rate is 100 L/h/panel. For
example, towards a swimming pool or geothermal probes.
-
For direct pool heating applications, the recommended nominal flow rate is 200 L/h/panel.
The curves below are given as an indication.